• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

8-502.6 New Fire Escapes and Fire Escape Ladders

California Historical Building Code 2019 > 8-5 Means of Egress > 8-502 General > 8-502.6 New Fire Escapes and Fire Escape Ladders
JUMP TO FULL CODE CHAPTER
New fire escapes and fire escape ladders which comply with this section shall be acceptable as one of the required means of egress. New fire escapes and new fire escape ladders shall comply with the following:
  1. Access from a corridor shall not be through an intervening room.
  2. All openings within 10 feet (3048 mm) shall be protected by three-fourths-hour fire assemblies. When located within a recess or vestibule, adjacent enclosure walls shall be of not less than one-hour fire-resistive construction.
  3. Egress from the building shall be by a clear opening having a minimum dimension of not less than 29 inches (737 mm). Such openings shall be openable from the inside without the use of a key or special knowledge or effort. The sill of an opening giving access shall not be more than 30 inches (737 mm) above the floor, step or landing of the building or balcony.
  4. Fire escape stairways and balconies shall support the dead load plus a live load of not less than 100 pounds per square foot (4.79 kN/m2) and shall be provided with a top and intermediate handrail on each side. The pitch of the stairway shall not exceed 72 degrees with a minimum width of 18 inches (457 mm). Treads shall not be less than 4 inches (102 mm) in width, and the rise between treads shall not exceed 10 inches (254 mm). All stair and balcony railings shall support a horizontal force of not less than 50 pounds per lineal foot (729.5 N/m2) of railing.
  5. Balconies shall not be less than 44 inches (1118 mm) in width with no floor opening other than the stairway opening greater than 5/8 inch (15.9 mm) in width. Stairway openings in such balconies shall not be less than 22 inches by 44 inches (559 by 1118 mm). The balustrade of each balcony shall not be less than 36 inches (914 mm) high with not more than 9 inches (287 mm) between balusters.
  6. Fire escapes shall extend to the roof or provide an approved gooseneck ladder between the top floor landing and the roof when serving buildings four or more stories in height having roofs with less than 4 units vertical in 12 units horizontal (33.3 percent slope). Fire escape ladders shall be designed and connected to the building to withstand a horizontal force of 100 pounds (445 N) placed anywhere on the rung. All ladders shall be at least 15 inches (381 mm) wide, located within 12 inches (305 mm) of the building. Ladder rungs shall be 3/4 inch (19.1 mm) in diameter and shall be located 12 inches (305 mm) on center. Openings for roof access ladders through cornices and similar projections shall have minimum dimensions of 30 inches by 33 inches (762 by 838 mm).
    The length of fire escapes and exit ladder devices shall be limited to that approved by the building official based on products listed by a recognized testing laboratory.
  7. The lowest balcony shall not be more than 18 feet (5486 mm) from the ground. Fire escapes shall extend to the ground or be provided with counterbalanced stairs reaching to the ground.
  8. Fire escapes shall not take the place of stairways required by the codes under which the building was constructed.
  9. Fire escapes shall be kept clear and unobstructed at all times and maintained in good working order.

Related Code Sections


8-502.6 Means of Egress, New Fire Escapes and Fire Escape Ladders
New fire escapes and fire escape ladders which comply with this section shall be acceptable as one of the required means of egress. New fire escapes ...
California Historical Building Code 2016 > 8-5 Means of Egress > 8-502 General > 8-502.6 New Fire Escapes and Fire Escape Ladders
8-502.6 Means of Egress, New Fire Escapes and Fire Escape Ladders
New fire escapes and fire escape ladders which comply with this section shall be acceptable as one of the required means of egress. New fire escapes ...
California Historical Building Code 2019 > 8-5 Means of Egress > 8-502 General > 8-502.6 New Fire Escapes and Fire Escape Ladders
504.1 Prescriptive Compliance Method, Where Permitted
or because of sidewalks, alleys or roads at grade level. New fire escapes shall not incorporate ladders or access by windows ...
California Existing Building Code 2019 > 5 Prescriptive Compliance Method > 504 Fire Escapes (Not Adopted by HCD) > 504.1 Where Permitted
405.1 Prescriptive Compliance Method, Where Permitted
or due to the sidewalks, alleys or roads at grade level. New fire escapes shall not incorporate ladders or access by windows ...
California Existing Building Code 2016 > 4 Prescriptive Compliance Method > 405 Fire Escapes > 405.1 Where Permitted
Section 504 Prescriptive Compliance Method, Fire Escapes (Not Adopted by HCD)
or because of sidewalks, alleys or roads at grade level. New fire escapes shall not incorporate ladders or access by windows ...
California Existing Building Code 2019 > 5 Prescriptive Compliance Method > 504 Fire Escapes (Not Adopted by HCD)
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING