905.2.1.1 Municipal Water Supply
JUMP TO FULL CODE CHAPTER
A municipal water supply capable of supplying the required standpipe flow rate with a residual pressure not less than 20 psi (1.4 bars) through a fire hydrant shall be provided. A fire hydrant shall be located within 300 feet (91 m) of the building's fire department connection.
Related Code Sections
905.2.1.1 Fire Protection Systems, Municipal Water Supply
A municipal water supply capable of supplying the required standpipe flow rate with a residual pressure not less than 20 psi (1.4 bars) through ...
Minnesota Fire Code 2015 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.2 Installation Standard > 905.2.1 Modification to Standards > 905.2.1.1 Municipal Water Supply
905.2.1.1 Fire Protection Systems, Municipal Water Supply
A municipal water supply capable of supplying the required standpipe flow rate with a residual pressure not less than 20 psi (1.4 bars) through ...
Minnesota Building Code 2015 > 9 Fire Protection Systems > 905 Standpipe Systems > 905.2 Installation Standard > 905.2.1 Modification to Standards > 905.2.1.1 Municipal Water Supply
(3) Special Conditions, Public Gas System, Municipal Water Supply
Prime movers shall not be solely dependent on a public utility gas system for their fuel supply or on a municipal water supply for their cooling ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 701 Legally Required Standby Systems > 701.12 General Requirements > (D) Generator Set > (3) Public Gas System, Municipal Water Supply
904.1.1 Alterations—Level 3, High-Rise Buildings
In high-rise buildings, work areas shall be provided with automatic sprinkler protection where the building has a sufficient municipal water supply ...
Minnesota Conservation Code for Existing Buildings 2015 > 9 Alterations—Level 3 > 904 Fire Protection > 904.1 Automatic Sprinkler Systems > 904.1.1 High-Rise Buildings
(3) Special Conditions, Dual Supplies
Prime movers shall not be solely dependent on a public utility gas system for their fuel supply or municipal water supply for their cooling systems ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 708 Critical Operations Power Systems (COPS) > 708.20 Sources of Power > (F) Generator Set > (3) Dual Supplies