722.4.1.3 Multiwythe Walls With Airspace
JUMP TO FULL CODE CHAPTER
(Equation 7-10)
Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined by the formula:

where:
R = The fire-resistance rating of the assembly (hours).
R1, R2 and Rn = The fire-resistance rating of the individual wythes (hours).
as = Coefficient for continuous airspace.
Values for Rn0.59 for use in Equation 7-10 are given in Table 722.4.1(3). The coefficient for each continuous airspace of 1/2 inch to 31/2 inches (12.7 to 89 mm) separating two individual wythes shall be 0.3.
Related Code Sections
722.4.1.3 Fire and Smoke Protection Features, Multiwythe Walls With Airspace
Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined by the formula ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.4 Clay Brick and Tile Masonry > 722.4.1 Masonry Walls > 722.4.1.3 Multiwythe Walls With Airspace
722.4.1.3 Fire and Smoke Protection Features, Multiwythe Walls With Airspace
Where a continuous airspace separates multiple wythes of the wall or partition, the total fire-resistance rating shall be determined ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.4 Clay Brick and Tile Masonry > 722.4.1 Masonry Walls > 722.4.1.3 Multiwythe Walls With Airspace
722.4.2 Fire and Smoke Protection Features, Multiwythe Walls
The fire-resistance rating for walls or partitions consisting of two or more dissimilar wythes shall be permitted to be determined by the formula ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.4 Clay Brick and Tile Masonry > 722.4.2 Multiwythe Walls
C402.2.7 [CE] Commercial Energy Efficiency, Airspaces
resistance of airspaces located on the exterior side of the continuous air barrier and adjacent to and behind the exterior wall-covering material shall ...
2018 Illinois Energy Conservation Code Standards for Privately Funded Commercial Facilities and Standards for Residential Buildings > 4 [CE] Commercial Energy Efficiency > C402 Building Envelope Requirements > C402.2 Specific Building Thermal Envelope Insulation Requirements (Prescriptive) > C402.2.7 Airspaces
722.4.2.1 Fire and Smoke Protection Features, Multiwythe Walls of Different Material
For walls that consist of two or more wythes of different materials (concrete or concrete masonry units ) in combination with clay masonry units ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.4 Clay Brick and Tile Masonry > 722.4.2 Multiwythe Walls > 722.4.2.1 Multiwythe Walls of Different Material