17.4.5.4 Multistory Buildings
Go To Full Code Chapter
17.4.5.4.1
In multistory buildings, riser supports shall be provided at the lowest level, at each alternate level above, above and below offsets, and at the top of the riser.
17.4.5.4.2*
Supports above the lowest level shall also restrain the pipe to prevent movement by an upward thrust where flexible fittings are used.
17.4.5.4.3
Where risers are supported from the ground, the ground support shall constitute the first level of riser support.
17.4.5.4.4
Where risers are offset or do not rise from the ground, the first ceiling level above the offset shall constitute the first level of riser support.
Related Code Sections
17.4.5.4 Installation Requirements for Hanging and Support of System Piping, Multistory Buildings
In multistory buildings, riser supports shall be provided at the lowest level, at each alternate level above, above and below offsets, and at the top ...
9.2.5.4 Hanging, Bracing, and Restraint of System Piping, Multistory Buildings
In multistory buildings, riser supports shall be provided at the lowest level, at each alternate level above, above and below offsets, and at the top ...
9.2.5.4 Hanging, Bracing, and Restraint of System Piping, Multistory Buildings
In multistory buildings, riser supports shall be provided at the lowest level, at each alternate level above, above and below offsets, and at the top ...
506.2.3 General Building Heights and Areas, Single-Occupancy, Multistory Buildings
The allowable area of a single-occupancy building with more than one story above grade plane shall be determined in accordance with Equation 5-2 ...
506.2.3 General Building Heights and Areas, Single-Occupancy, Multistory Buildings
The allowable area of a single-occupancy building with more than one story above grade plane shall be determined in accordance with Equation 5-2 ...