408.2.2 Multiple Showerheads Serving One Shower [BSC-CG]
JUMP TO FULL CODE CHAPTER
When a shower is served by more than one
showerhead, the combined flow rate of all showerheads
and/or other shower outlets controlled by a single valve shall
not exceed 1.8 gallons(6.81 L) per minute at 80 psi, or the
shower shall be designed to allow only one shower outlet
to be in operation at a time in compliance with Chapter
5, Division 5.3 of the California Green Building
Standards Code (CALGreen).
Note: A hand-held shower shall be considered a showerhead.
Note: A hand-held shower shall be considered a showerhead.
Related Code Sections
408.2.2 Plumbing Fixtures and Fixture Fittings, Multiple Showerheads Serving One Shower [BSC-CG]
When a shower is served by more than one
showerhead, the combined flow rate of all showerheads
and/or other shower outlets controlled by a single ...
California Plumbing Code 2016 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.2 Water Consumption [HCD 1] > 408.2.2 Multiple Showerheads Serving One Shower [BSC-CG]
5.303.3.3 Nonresidential Mandatory Measures, Showerheads. [BSC-CG]
When a shower is served by more than one
showerhead, the combined flow rate of all showerheads
and/or other shower outlets controlled ...
California Green Building Standards Code 2016 > 5 Nonresidential Mandatory Measures > 5.303 Indoor Water Use > 5.303.3 Water Conserving Plumbing Fixtures and Fittings > 5.303.3.3 Showerheads. [BSC-CG]
408.2.2 Plumbing Fixtures and Fixture Fittings, Multiple Showerheads Serving One Shower
[BSC-CG, DSA-SS & DSA-SS/CC] When a shower is served by more than one showerhead, the combined
flow rate of all showerheads and/or other shower ...
California Plumbing Code 2019 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.2 Water Consumption > 408.2.2 Multiple Showerheads Serving One Shower
408.2 Plumbing Fixtures and Fixture Fittings, Water Consumption
). [BSC-CG, DSA-SS & DSA-SS/CC] When a shower is served by more than one showerhead, the combined
flow ...
California Plumbing Code 2019 > 4 Plumbing Fixtures and Fixture Fittings > 408.0 Showers > 408.2 Water Consumption
4.303.1.3 Residential Mandatory Measures, Showerheads
When a shower is served by more than one
showerhead, the combined flow rate of all showerheads
and/or other shower outlets controlled ...
California Green Building Standards Code 2019 > 4 Residential Mandatory Measures > 4.303 Indoor Water Use > 4.303.1 Water Conserving Plumbing Fixtures and Fittings > 4.303.1.3 Showerheads