26.7.3.12 Multiple Pumps
JUMP TO FULL CODE CHAPTER
Where two fire pumps are required to ensure the reliability of the water supply, each fire pump shall meet the requirements of 26.7.3.1 through 26.7.3.4.
In addition, a system that is required to have more than one pump shall be designed to accommodate the following features:
- *Pump controls and system sensors shall be arranged such that the secondary pump will automatically operate if the primary pump fails to operate or deliver the required water pressure and flow. [Figure A.26.7.3.12.2(1) is an example of an acceptable dual pump arrangement.]
- Both pumps shall be served from normal and emergency power sources. However, where approved by the authority having jurisdiction, the secondary pump shall be permitted to be nonelectrically driven.
- Pump failure or operation shall be indicated at the central safety station.
Related Code Sections
26.7.3.12 Marine Systems, Multiple Pumps
Where two fire pumps are required to ensure the reliability of the water supply, each fire pump shall meet the requirements of 26.7.3.1 through ...
Standard for the Installation of Sprinkler Systems 2013 of New York State > 26 Marine Systems > 26.7 Water Supplies > 26.7.3 Fire Pump > 26.7.3.12 Multiple Pumps
26.7.3.12 Marine Systems, Multiple Pumps
Where two fire pumps are required to ensure the reliability of the water supply, each fire pump shall meet the requirements of 26.7.3.1 through ...
Standard for the Installation of Sprinkler Systems 2016 of New York State > 26 Marine Systems > 26.7 Water Supplies > 26.7.3 Fire Pump > 26.7.3.12 Multiple Pumps
R326.6.4 Building Planning, Dual Drain Separation
Single or multiple pump circulation systems have a
minimum of two suction outlets of the approved type. A minimum horizontal or vertical
distance ...
Residential Code 2015 of New York State > 3 Building Planning > R326 Swimming Pools, Spas and Hot Tubs > R326.6 Entrapment Protection for Swimming Pool and Spa Suction Outlets > R326.6.4 Dual Drain Separation
G106.4 Swimming Pools, Spas and Hot Tubs, Dual Drain Separation
Single or multiple pump circulation systems have a minimum of two suction outlets of the approved type. A minimum horizontal or vertical distance ...
2010 Residential Code of NY > G Swimming Pools, Spas and Hot Tubs > G106 Entrapment Protection for Swimming Pool and Spa Suction Outlets > G106.4 Dual Drain Separation
503.4.3.4 Commercial Energy Efficiency, Part Load Controls
of design flow rate utilizing adjustable speed drive(s) on pump(s), or multiple-staged pumps where at least one-half of the total pump horsepower ...
2010 Energy Conservation Code of NY > 5 Commercial Energy Efficiency > 503 Building Mechanical Systems > 503.4 Complex HVAC Systems and Equipment (Prescriptive) > 503.4.3 Hydronic Systems Controls > 503.4.3.4 Part Load Controls