// CODE SNIPPET
3206.3.2 Multiple High-Piled Storage Areas
JUMP TO FULL CODE CHAPTER
Where a building contains multiple high-piled storage areas, the aggregate of all high-piled storage areas shall be used for the application of Table 3206.2 unless the high-piled storage areas are separated in accordance with one of the following:
- High-piled storage areas separated by fire barriers with a minimum fire-resistance-rating of 1 hour constructed in accordance with Section 707 of the International Building Code.
- In buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, high-piled storage areas separated by 100 feet (30 480 mm) or more. The area providing the separation shall not contain high-piled combustible storage.
High-piled storage areas classified as Class I through IV not separated from high-piled storage areas classified as high hazard shall utilize the aggregate of all high-piled storage areas as high hazard for the purposes of the application of Table 3206.2. Multiple class high-piled storage areas meeting the separation requirements in Section 3206.3.2 shall be considered as separated. The fire safety features in Table 3206.2 shall be extended beyond the higher-hazard storage area in accordance with Section 3206.2.1.
Exception: Multiple class high-piled storage areas do not need to be separated where in accordance with Section 3204.2.
Related Code Sections
3206.3.2 High-Piled Combustible Storage, Multiple High-Piled Storage Areas
Where a building contains multiple high-piled storage areas , the aggregate of all high-piled storage areas shall be used for the application ...
Fire Code 2021 of Colorado > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.3 High-Piled Storage Areas > 3206.3.2 Multiple High-Piled Storage Areas
3206.3.2 High-Piled Combustible Storage, Multiple High-Piled Storage Areas
Where a building contains multiple high-piled storage areas , the aggregate of all high-piled storage areas shall be used for the application ...
Fire Code 2018 of Colorado > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.3 High-Piled Storage Areas > 3206.3.2 Multiple High-Piled Storage Areas
Section 3206 High-Piled Combustible Storage, General Fire Protection and Life Safety Features
a building contains multiple high-piled storage areas , the aggregate of all high-piled storage areas shall be used for the application of Table 3206.2 ...
Fire Code 2018 of Colorado > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features
3206.10.1.1 High-Piled Combustible Storage, Sprinklered Buildings
-piled storage areas exceeding 2,500 square feet (232 m 2 ) in area, that are accessible to the public and designated to contain high-hazard commodities ...
Fire Code 2021 of Colorado > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.10 Aisles > 3206.10.1 Width > 3206.10.1.1 Sprinklered Buildings
3206.10.1.1 High-Piled Combustible Storage, Sprinklered Buildings
-piled storage areas exceeding 2,500 square feet (232 m 2 ) in area, that are accessible to the public and designated to contain high-hazard commodities ...
Fire Code 2018 of Colorado > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.10 Aisles > 3206.10.1 Width > 3206.10.1.1 Sprinklered Buildings