If the sources in 695.3(A) are not practicable and the installation is part of a multibuilding campus-style complex, feeder sources shall be permitted if approved by the authority having jurisdiction and installed in accordance with either 695.3(C)(1) and (C)(3) or (C)(2) and (C)(3).
(1) Feeder Sources
Two or more feeders shall be permitted as more than one power source if such feeders are connected to, or derived from, separate utility services. The connection(s), overcurrent protective device(s), and disconnecting means for such feeders shall meet the requirements of 695.4(B)(1)(b).
(2) Feeder and Alternate Source
A feeder shall be permitted as a normal source of power if an alternate source of power independent from the feeder is provided. The connection(s), overcurrent protective device(s), and disconnecting means for such feeders shall meet the requirements of 695.4(B)(1)(b).
(3) Selective Coordination
Overcurrent protective device(s) shall be selectively coordinated with all supply-side overcurrent protective device(s).
Selective coordination shall be selected by a licensed professional engineer or other qualified persons engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, maintain, and operate the system.
Exception: Selective coordination shall not be required between two over-current devices located in series if no loads are connected in parallel with the downstream device.

Related Code Sections

(C) Special Equipment, Multibuilding Campus-Style Complexes
If the sources in 695.3(A) are not practicable and the installation is part of a multibuilding campus-style complex, feeder sources shall ...
(C) Special Equipment, Multibuilding Campus-Style Complexes
If the sources in 695.3(A) are not practicable and the installation is part of a multibuilding campus-style complex, feeder sources shall ...
(3) Special Equipment, Selective Coordination
Overcurrent protective device(s) shall be selectively coordinated with all supply-side overcurrent protective device(s). Selective coordination shall ...
(3) Special Equipment, Disconnecting Means
at the same time would be unlikely. Exception to 695.4(B)(3)(a): For a multibuilding campus-style complex(s) installed under the provisions of 695.3(C ...
(3) Special Equipment, Disconnecting Means
operation at the same time would be unlikely. Exception to 695.4(B)(3)(a): For a multibuilding campus-style complex(s) installed under ...