Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

2311.8.4 Motor Vehicle Repair Booths

Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels > 2311.8.4 Motor Vehicle Repair Booths
JUMP TO FULL CODE CHAPTER
The design and construction of motor vehicle repair booths shall be in accordance with Sections 2311.8.4.1 through 2311.8.4.4.

2311.8.4.1 Construction

Motor vehicle repair booths shall be constructed of approved noncombustible materials. Where walls or ceiling assemblies are constructed of sheet metal, single-skin assemblies shall be not thinner than 0.0478 inch (18 gage) (1.2 mm) and each sheet of double-skin assemblies shall be not thinner than 0.0359 inch (20 gage) (0.9 mm). Structural sections of motor vehicle repair booths shall be sealed in an approved manner.

2311.8.4.2 Surfaces

The interior surfaces of motor vehicle repair booths shall be constructed to permit the free passage of exhaust air from all parts of the interior.

2311.8.4.3 Means of Egress

Means of egress shall be provided in accordance with Chapter 10.
Exception: Means of egress doors from premanufactured motor vehicle repair booths shall be not less than 30 inches (762 mm) in width by 80 inches (2032 mm) in height.

2311.8.4.4 Clear Space

Motor vehicle repair booths shall be installed so that all parts of the booth be provided with ready access for cleaning. A clear area of not less than 3 feet (914 mm) wide shall be maintained on all sides of the motor vehicle repair booth. This clear area shall be kept free of any storage or combustible construction.
Exceptions:
  1. This requirement shall not prohibit locating a motor vehicle repair booth closer than 3 feet (914 mm) to or directly against an interior partition, wall or floor/ceiling assembly that has a fire-resistance rating of not less than 1 hour, provided that the motor vehicle repair booth can be adequately maintained and cleaned.
  2. This requirement shall not prohibit locating a motor vehicle repair booth closer than 3 feet (914 mm) to an exterior wall or a roof assembly, provided that the wall or roof is constructed of noncombustible material and the motor vehicle repair booth can be adequately maintained and cleaned.

Related Code Sections


2311.8.4 Motor Fuel-Dispensing Facilities and Repair Garages, Motor Vehicle Repair Booths
The design and construction of motor vehicle repair booths shall be in accordance with Sections 2311.8.4.1 through 2311.8.4.4 ...
Fire Code 2021 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels > 2311.8.4 Motor Vehicle Repair Booths
2311.8.4 Motor Fuel-Dispensing Facilities and Repair Garages, Motor Vehicle Repair Booths
The design and construction of motor vehicle repair booths shall be in accordance with Sections 2311.8.4.1 through 2311.8.4.4 ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels > 2311.8.4 Motor Vehicle Repair Booths
2311.8.7 Motor Fuel-Dispensing Facilities and Repair Garages, Fire Extinguishers
Portable fire extinguishers complying with Section 906 shall be provided for motor vehicle repair rooms, motor vehicle repair booths or motor vehicle ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels > 2311.8.7 Fire Extinguishers
2311.8 Motor Fuel-Dispensing Facilities and Repair Garages, Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels
The room, motor vehicle repair booth or motor vehicle repair space containing repair garage activities for the conversion or repair of vehicles ...
Fire Code 2018 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels
2311.8.4.1 Motor Fuel-Dispensing Facilities and Repair Garages, Construction
Motor vehicle repair booths shall be constructed of approved noncombustible materials. Where walls or ceiling assemblies are constructed of sheet ...
Fire Code 2021 of Colorado > 23 Motor Fuel-Dispensing Facilities and Repair Garages > 2311 Repair Garages > 2311.8 Repair Garages for Vehicles Fueled by Lighter-Than-Air Fuels > 2311.8.4 Motor Vehicle Repair Booths > 2311.8.4.1 Construction
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING