406.7 Motor Fuel-Dispensing Facilities
JUMP TO FULL CODE CHAPTER
Motor fuel-dispensing facilities shall comply with the International Fire Code and Sections 406.2 and 406.7.
Canopies under which fuels are dispensed shall have a clear, unobstructed height of not less than 13 feet 6 inches (4115 mm) to the lowest projecting element in the vehicle drive-through area. Canopies and their supports over pumps shall be of noncombustible materials, fire-retardant-treated wood complying with Chapter 23, heavy timber complying with Section 2304.11 or construction providing 1-hour fire resistance. Combustible materials used in or on a canopy shall comply with one of the following:
- Shielded from the pumps by a noncombustible element of the canopy, or heavy timber complying with Section 2304.11.
- Plastics covered by aluminum facing having a thickness of not less than 0.010 inch (0.30 mm) or corrosion-resistant steel having a base metal thickness of not less than 0.016 inch (0.41 mm). The plastic shall have a flame spread index of 25 or less and a smoke-developed index of 450 or less when tested in the form intended for use in accordance with ASTM E84 or UL 723 and a self-ignition temperature of 650°F (343°C) or greater when tested in accordance with ASTM D1929.
- Panels constructed of light-transmitting plastic materials shall be permitted to be installed in canopies erected over motor vehicle fuel-dispensing station fuel dispensers, provided that the panels are located not less than 10 feet (3048 mm) from any building on the same lot and face yards or streets not less than 40 feet (12 192 mm) in width on the other sides. The aggregate areas of plastics shall be not greater than 1,000 square feet (93 m2). The maximum area of any individual panel shall be not greater than 100 square feet (9.3 m2).
Canopies that are used to shelter dispensing operations where flammable compressed gases are located on the roof of the canopy shall be in accordance with the following:
Related Code Sections
309.3 Occupancy Classification and Use, Motor Fuel-Dispensing Facilities
Motor fuel-dispensing facilities shall comply with Section 406.7 ...
Building Code 2021 of Illinois > 3 Occupancy Classification and Use > 309 Mercantile Group M > 309.3 Motor Fuel-Dispensing Facilities
406.7 Special Detailed Requirements Based on Occupancy and Use, Motor Fuel-Dispensing Facilities
Motor fuel-dispensing facilities shall comply with the International Fire Code and Sections 406.2 and 406.7 ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 406 Motor-Vehicle-Related Occupancies > 406.7 Motor Fuel-Dispensing Facilities
406.7 Special Detailed Requirements Based on Occupancy and Use, Motor Fuel-Dispensing Facilities
Motor fuel-dispensing facilities shall comply with the International Fire Code and Sections 406.2 and 406.7 ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 406 Motor-Vehicle-Related Occupancies > 406.7 Motor Fuel-Dispensing Facilities
Article 514 Special Occupancies, Motor Fuel Dispensing Facilities
This article shall apply to motor fuel dispensing facilities, marine/motor fuel ...
National Electrical Code 2017 of Illinois > 5 Special Occupancies > 514 Motor Fuel Dispensing Facilities
Article 514 Special Occupancies, Motor Fuel Dispensing Facilities
This article shall apply to motor fuel dispensing facilities, marine/motor fuel dispensing facilities, motor fuel dispensing facilities located ...
National Electrical Code 2020 of Illinois > 5 Special Occupancies > 514 Motor Fuel Dispensing Facilities