• Codes
  • Features
  • Pricing
  • Sign Up
  • Log in
Log in
Sign Up
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Contact
  • Terms
  • Privacy
// CODE SNIPPET

Section 409 Motion Picture Projection Rooms

Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms
JUMP TO FULL CODE CHAPTER

409.1 General

The provisions of Sections 409.1 through 409.5 shall apply to rooms in which ribbon-type cellulose acetate or other safety film is utilized in conjunction with electric arc, xenon or other light-source projection equipment that develops hazardous gases, dust or radiation. Where cellulose nitrate film is utilized or stored, such rooms shall comply with NFPA 40.

409.1.1 Projection Room Required

Every motion picture machine projecting film as mentioned within the scope of this section shall be enclosed in a projection room. Appurtenant electrical equipment, such as rheostats, transformers and generators, shall be within the projection room or in an adjacent room of equivalent construction.

409.2 Construction of Projection Rooms

Every projection room shall be of permanent construction consistent with the construction requirements for the type of building in which the projection room is located. Openings are not required to be protected.

The room shall have a floor area of not less than 80 square feet (7.44 m2) for a single machine and not less than 40 square feet (3.7 m2) for each additional machine. Each motion picture projector, floodlight, spotlight or similar piece of equipment shall have a clear working space of not less than 30 inches by 30 inches (762 mm by 762 mm) on each side and at the rear thereof, but only one such space shall be required between two adjacent projectors. The projection room and the rooms appurtenant thereto shall have a ceiling height of not less than 7 feet 6 inches (2286 mm). The aggregate of openings for projection equipment shall not exceed 25 percent of the area of the wall between the projection room and the auditorium. Openings shall be provided with glass or other approved material, so as to close completely the opening.

409.3 Projection Room and Equipment Ventilation

Ventilation shall be provided in accordance with the International Mechanical Code.

409.3.1 Supply Air

Each projection room shall be provided with adequate air supply inlets so arranged as to provide well-distributed air throughout the room. Air inlet ducts shall provide an amount of air equivalent to the amount of air being exhausted by projection equipment. Air is permitted to be taken from the outside; from adjacent spaces within the building, provided the volume and infiltration rate is sufficient; or from the building air-conditioning system, provided it is so arranged as to provide sufficient air when other systems are not in operation.

409.3.2 Exhaust Air

Projection rooms are permitted to be exhausted through the lamp exhaust system. The lamp exhaust system shall be positively interconnected with the lamp so that the lamp will not operate unless there is the required airflow. Exhaust air ducts shall terminate at the exterior of the building in such a location that the exhaust air cannot be readily recirculated into any air supply system. The projection room ventilation system is permitted to also serve appurtenant rooms, such as the generator and rewind rooms.

409.3.3 Projection Machines

Each projection machine shall be provided with an exhaust duct that will draw air from each lamp and exhaust it directly to the outside of the building. The lamp exhaust is permitted to serve to exhaust air from the projection room to provide room air circulation. Such ducts shall be of rigid materials, except for a flexible connector approved for the purpose. The projection lamp or projection room exhaust system, or both, is permitted to be combined but shall not be interconnected with any other exhaust or return system, or both, within the building.

409.4 Lighting Control

Provisions shall be made for control of the auditorium lighting and the means of egress lighting systems of theaters from inside the projection room and from not less than one other convenient point in the building.

409.5 Miscellaneous Equipment

Each projection room shall be provided with rewind and film storage facilities.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 409 Special Detailed Requirements Based on Occupancy and Use, Motion Picture Projection Rooms
Each projection room shall be provided with adequate air supply inlets so arranged as to provide well-distributed ...
Building Code 2018 of Utah > 4 Special Detailed Requirements Based on Occupancy and Use > 409 Motion Picture Projection Rooms
Section 409 Special Detailed Requirements Based on Use and Occupancy, Motion Picture Projection Rooms
with NFPA 40. Every motion picture machine projecting ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms
409.1 Special Detailed Requirements Based on Use and Occupancy, General
Every motion picture machine projecting film as mentioned within the scope of this section shall be enclosed in a projection room ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms > 409.1 General
409.5 Special Detailed Requirements Based on Occupancy and Use, Miscellaneous equipment
Each projection room shall be provided with rewind and film storage facilities ...
Building Code 2018 of Utah > 4 Special Detailed Requirements Based on Occupancy and Use > 409 Motion Picture Projection Rooms > 409.5 Miscellaneous equipment
409.5 Special Detailed Requirements Based on Use and Occupancy, Miscellaneous Equipment
Each projection room shall be provided with rewind and film storage facilities ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 409 Motion Picture Projection Rooms > 409.5 Miscellaneous Equipment
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US