22.19 Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations
Go To Full Code Chapter
22.19.1 Design Requirements. (Reserved)
22.19.2 Installation Requirements
22.19.2.1
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:4.11.1.3.1]
22.19.2.2
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard, Group 2. [140:4.11.1.3.2]
22.19.2.3
In any production location building protected by an existing automatic sprinkler system, where solid- or hard- ceiling sets or platforms are introduced and create an obstruction to sprinkler discharge, the provisions of 22.19.2.4 or 22.19.2.5 shall be met. [140:5.11.3]
22.19.2.4*
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:5.11.4]
22.19.2.5*
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard, Group 2. [140:5.11.5]
Upcodes Diagrams
Related Code Sections
22.19 Special Occupancy Requirements, Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations
:4.11.1.3.2] In any production location building protected ...
22.19.2.2 Special Occupancy Requirements,
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design ...
22.19.2.5* Special Occupancy Requirements,
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design ...
2.4 Referenced Publications, References for Extracts in Mandatory Sections
Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations, 2013 edition. NFPA 150, Standard ...
2.4 Referenced Publications, References for Extracts in Mandatory Sections
, Standard on Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations, 2008 edition. NFPA 150 ...