2122.8 Mortar and Grout
JUMP TO FULL CODE CHAPTER
Vertical alignment of cells to be grouted shall maintain clear, unobstructed, continuous, vertical cores measuring not less than 21/2 inches by 3 inches (51 mm by 76 mm) for fine aggregate grout and 3 inches by 3 inches (76 mm by 76 mm) for coarse aggregate grout as defined by ASTM C476. The architect or engineer may specify other grout space sizes which shall be permitted provided they comply with TMS 402 Section 1.203.2.1 and TMS 602 Section 3.5C.
Placing of mortar and masonry units shall comply with TMS 602 Section 3.3.
Grout placement shall be in accordance with TMS 402 and TMS602.
Confine grout to the areas indicated on the project drawings. Use material to confine grout that permits bond between masonry units and mortar.
Grout shall be placed before any initial set has occurred, but in no case more than 11/2 hours after the mix-designed water has been added.
Grouting shall be consolidated between lifts by puddling, rodding or mechanical vibration.
Related Code Sections
2122.8 Masonry, Mortar and Grout
Mortar materials shall comply with TMS 602/ACI 530.1/ASCE 6 Section 2.1. Grout materials shall comply with TMS 602/ACI 530.1/ASCE 6 Section 2.2 ...
2014 FBC - Building, 5th edition > 21 Masonry > 2122 High-Velocity Hurricane Zones— Reinforced Unit Masonry > 2122.8 Mortar and Grout
2122.8 Masonry, Mortar and Grout
Mortar materials shall comply with TMS 602 Section 2.1. Grout materials shall comply with TMS 602 Section 2.2 ...
2020 FBC - Building, 7th edition > 21 Masonry > 2113 Masonry Chimneys > 2122 High-Velocity Hurricane Zones— Reinforced Unit Masonry > 2122.8 Mortar and Grout
2122.8 Masonry, Mortar and Grout
Mortar materials shall comply with TMS 602/ACI 530.1/ASCE 6 Section 2.1. Grout materials shall comply with TMS 602/ACI 530.1/ASCE 6 Section 2.2 ...
2017 FBC - Building, 6th edition > 21 Masonry > 2122 High-Velocity Hurricane Zones— Reinforced Unit Masonry > 2122.8 Mortar and Grout
2103.11.4 Masonry, Furan Mortar and Grout
Chemical-resistant furan mortar and grout that are used to install ceramic tile shall comply with ANSI A118.5. Tile set and grouted with furan shall ...
2014 FBC - Building, 5th edition > 21 Masonry > 2103 Masonry Construction Materials > 2103.11 Mortars for Ceramic Wall and Floor Tile > 2103.11.4 Furan Mortar and Grout
2103.2.3.4 Masonry, Furan Mortar and Grout
Chemical-resistant furan mortar and grout that are used to install ceramic tile shall comply with ANSI A118.5. Tile set and grouted with furan shall ...
2020 FBC - Building, 7th edition > 21 Masonry > 2103 Masonry Construction Materials > 2103.2 Mortar > 2103.2.3 Mortars for Ceramic Wall and Floor Tile > 2103.2.3.4 Furan Mortar and Grout