3309.4.4 Monitoring
JUMP TO FULL CODE CHAPTER
During the course of excavation work the following shall be monitored in accordance with Section 3309.16:
- Buildings that are within a distance from the edge of the excavation that is equal to or less than the maximum depth of the excavation.
- Historic structures that are contiguous to or within a lateral distance of 90 feet (27 432 mm) from the edge of the lot where an excavation is occurring.
- The excavation occurs more than 5 feet (1524 mm) from all footings and foundations; or
- Where the excavation occurs within five feet (1524 mm) or less from a footing or foundation, such excavation does not occur below the level of the footing or foundation.
Related Code Sections
1704.20.7.1 Structural Tests and Special Inspections, Monitoring
The design documents shall include any requirements for monitoring of the subject structure and/or adjacent structures, as determined ...
NYC Building Code 2014 > 17 Structural Tests and Special Inspections > 1704 Special Inspections > *1704.20 Structural Stability > 1704.20.7 Design Documents > 1704.20.7.1 Monitoring
1814.3 Soils and Foundations, Monitoring
When excavation, foundation construction, or underpinning is required, adjacent structures and properties shall be monitored in accordance ...
NYC Building Code 2014 > 18 Soils and Foundations > 1814 Underpinning and Support of Adjacent Property > 1814.3 Monitoring
3309.4.4 Safeguards During Construction or Demolition, Monitoring
During the course of excavation work the following shall be monitored in accordance with Section 3309.16: Buildings that are within a distance from ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3309 Protection of Adjoining Property > 3309.4 Soil or Foundation Work Affecting Adjoining Property > 3309.4.4 Monitoring
904.3.5 Fire Protection Systems, Monitoring
Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system ...
NYC Building Code 2008 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.3 Installation > 904.3.5 Monitoring
904.3.5 Fire Protection Systems, Monitoring
Where a fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the fire alarm system in accordance with NFPA 72 ...
NYC Building Code 2014 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.3 Installation > 904.3.5 Monitoring