903.3.1.6 Modifications to Sprinkler Standards
JUMP TO FULL CODE CHAPTER
When, in the opinion of the fire chief, an adequate alternate water supply for hose stream requirements is provided or available, the water supply requirements for the sprinkler system hose stream demands may be modified.
(Repealed).
Sprinkler protection need not be provided on the ceiling of rooms containing swimming pools when the pool area is used exclusively for swimming purposes and when sprinklers are provided around the perimeter of the pool area.
8.15.8.2 Linen closets and pantries.
Sprinklers are not required in linen closets and pantries within dwelling units that meet the following conditions:
Sprinklers are not required in linen closets and pantries within dwelling units that meet the following conditions:
- The area of the space does not exceed 12 square feet (1.1 m2);
- the least dimension does not exceed 3 feet (0.9 m);
- the walls and materials are surfaced with noncombustible or limited combustible materials; and
- the closet or pantry contains no mechanical equipment, electrical equipment, or electrical appliances.
8.17.2.5 Valves.
8.17.2.5.1 Fire department connection.
A listed check valve shall be installed in each fire department connection.
A listed check valve shall be installed in each fire department connection.
8.17.2.5.1.1 Maximum pipe length.
There shall be a maximum of 25 feet (7.6 m) of pipe between the check valve and the fire department connection inlet.
There shall be a maximum of 25 feet (7.6 m) of pipe between the check valve and the fire department connection inlet.
Exception: This maximum shall not apply to the check valve serving a free-standing fire department connection.
8.17.2.5.1.2 Check valve location.
The check valve shall be located to minimize freezing potential.
The check valve shall be located to minimize freezing potential.
Sprinkler protection is not required in vestibules that meet all of the following conditions:
- The vestibule is 225 square feet or less in floor area;
- The vestibule is of noncombustible or limited combustible construction;
- The vestibule has glazing allowing vision into vestibule;
- The vestibule's only purpose is ingress and egress; and
- The vestibule contains no fueled equipment, flammable or combustible liquids, or furniture. Incidental combustible storage in the vestibule is limited to 5 ft3 of material.
Related Code Sections
903.3.1.6 Fire Protection and Life Safety Systems, Modifications to Sprinkler Standards
The sprinkler installation standards as referenced in Sections 903.3.1.1, 903.3.1.2, and 903.3.1.3 are modified as follows ...
2020 Minnesota State Fire Code > 9 Fire Protection and Life Safety Systems > 903 Automatic Sprinkler Systems > 903.3 Installation Requirements > 903.3.1 Standards > 903.3.1.6 Modifications to Sprinkler Standards
903.3.1.6 Fire Protection Systems, Modifications to Sprinkler Standards
The sprinkler installation standards as referenced in Sections 903.3.1.1, 903.3.1.2, and 903.3.1.3 are modified as follows ...
Minnesota Fire Code 2015 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.3 Installation Requirements > 903.3.1 Standards > 903.3.1.6 Modifications to Sprinkler Standards
903.3.1.6 Fire Protection Systems, Modifications to Sprinkler Standards
The sprinkler installation standards as referenced in Sections 903.3.1.1, 903.3.1.2, and 903.3.1.3.are modified as follows ...
Minnesota Building Code 2015 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.3 Installation Requirements > 903.3.1 Standards > 903.3.1.6 Modifications to Sprinkler Standards
903.3.1.6.2 Fire Protection Systems, Elevator Shafts and Equipment
Sprinkler protection shall not be installed in elevator shafts, elevator pits or elevator machine rooms. Exception: Health care occupancies ...
Minnesota Fire Code 2015 > 9 Fire Protection Systems > 903 Automatic Sprinkler Systems > 903.3 Installation Requirements > 903.3.1 Standards > 903.3.1.6 Modifications to Sprinkler Standards > 903.3.1.6.2 Elevator Shafts and Equipment