R301.2.1.2.1 Modifications to ASTM E 1996
JUMP TO FULL CODE CHAPTER
Section 6.2.2 of ASTM E 1996 shall be modified as follows:
6.2.2 Unless otherwise specified, select the wind zone based on the ultimate design wind speed, Vult as follows:
6.2.2.1 Wind Zone 1 - 130 mph (58 m/s) ≤ ultimate design wind speed, Vult < 140 mph (62.5 m/s), and Hawaii.
6.2.2.2 Wind Zone 2 - 140 mph (62.5 m/s) ≤ ultimate design wind speed, Vult < 150 mph (67m/s) at greater than one mile (1.6 km) from the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.3 Wind Zone 3 - 150 mph (67 m/s) ≤ ultimate design wind speed, Vult ≤ 170 mph (76 m/s), or 140 mph (62.5 m/s) ≤ ultimate design wind speed, Vult ≤ 170 mph (76 m/s) and within one mile (1.6 km) of the coastline. The coastline shall be measured from the mean high water mark.
6.2.2.4 Wind Zone 4 - ultimate design wind speed, Vult > 170 mph (76 m/s).
Table 1 of ASTM E 1886 and ASTM E 1996 — add column and notes to read as follows:
Air Pressure Cycles
0.2 to 0.5 Ppos1
0.0 to 0.6 Ppos
0.5 to 0.8 Ppos
0.3 to 1.0 Ppos
0.3 to 1.0 Pneg2
0.5 to 0.8 Pneg
0.0 to 0.6 Pneg
0.2 to 0.5 Pneg
Notes:
- Ppos = 0.6 × positive ultimate design load in accordance with ASCE 7.
- Pneg = 0.6 × negative ultimate design load in accordance with ASCE 7.
Related Code Sections
R301.2.1.2.1 Building Planning, Modifications to ASTM E 1996
Section 6.2.2 of ASTM E 1996 shall be modified as follows: 6.2.2 Unless otherwise specified, select the wind zone based on the ultimate design wind ...
2014 FBC - Residential, 5th edition > 3 Building Planning > R301 Design Criteria > R301.2 Climatic and Geographic Design Criteria > R301.2.1 Wind Design Criteria > R301.2.1.2 Protection of Openings > R301.2.1.2.1 Modifications to ASTM E 1996
1609.1.2.2.1 Structural Design,
Modifications to ASTM E 1886 and ASTM E 1996. Table 1 of ASTM E 1886 and ASTM E 1996—revise the third column to read as follows: Air Pressure ...
2014 FBC - Building, 5th edition > 16 Structural Design > 1609 Wind Loads > 1609.1 Applications > 1609.1.2 Protection of Openings > 1609.1.2.2 Application of ASTM E 1996 > 1609.1.2.2.1
(E) Special Occupancies, Modifications to Classification
Areas adjacent to classified locations in which flammable vapors are not likely to be released, such as stock rooms, switchboard rooms, and other ...
National Electrical Code 2017 of Florida > 5 Special Occupancies > 511 Commercial Garages, Repair and Storage > 511.3 Area Classification, General > (E) Modifications to Classification
453.25.4.1 Special Detailed Requirements Based on Use and Occupancy, Missile Impact Criteria
walls and roofs, the missile criteria are as provided in ASTM E 1886 and ASTM E 1996 or SBC/SSTD 12 ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 453 State Requirements for Educational Facilities > 453.25 Public Shelter Design Criteria > 453.25.4 Structural Standard for Wind Loads > 453.25.4.1 Missile Impact Criteria
R612.3.1 Wall Construction, Comparative Analysis
the maximum cyclic pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E 1886 and ASTM E 1996 where applicable.
Nonoperable ...
2014 FBC - Residential, 5th edition > 6 Wall Construction > R612 Exterior Windows and Doors > R612.3 Testing and Labeling > R612.3.1 Comparative Analysis