507.4.1 Mixed Occupancy Buildings With Groups A-1 and A-2
JUMP TO FULL CODE CHAPTER
Group A-1 and A-2 occupancies of other than Type V construction shall be permitted within mixed occupancy buildings of unlimited area complying with Section 507.4, provided all of the following criteria are met:
- Group A-1 and A-2 occupancies are separated from other occupancies as required for separated occupancies in Section 508.4.4 with no reduction allowed in the fire-resistance rating of the separation based upon the installation of an automatic sprinkler system.
- Each area of the portions of the building used for Group A-1 or A-2 occupancies shall not exceed the maximum allowable area permitted for such occupancies in Section 503.1.
- Exit doors from Group A-1 and A-2 occupancies shall discharge directly to the exterior of the building.
Related Code Sections
507.4.1 General Building Heights and Areas, Mixed Occupancy Buildings With Groups A-1 and A-2
Group A-1 and A-2 occupancies of other than Type V construction shall be permitted within mixed occupancy buildings of unlimited area complying ...
Building Code 2021 of Illinois > 5 General Building Heights and Areas > 507 Unlimited Area Buildings > 507.4 Sprinklered, One-Story Buildings > 507.4.1 Mixed Occupancy Buildings With Groups A-1 and A-2
507.4.1 General Building Heights and Areas, Mixed Occupancy Buildings With Groups A-1 and A-2
Group A-1 and A-2 occupancies of other than Type V construction shall be permitted within mixed occupancy buildings of unlimited area complying ...
Building Code 2018 of Illinois > 5 General Building Heights and Areas > 507 Unlimited Area Buildings > 507.4 Sprinklered, One-Story Buildings > 507.4.1 Mixed Occupancy Buildings With Groups A-1 and A-2
1301.6.16 Performance Compliance Methods, Mixed Occupancies
Where a building has two or more occupancies that are not in the same occupancy classification, the separation between the mixed occupancies shall ...
Existing Building Code 2018 of Illinois > 13 Performance Compliance Methods > 1301 General > 1301.6 Evaluation Process > 1301.6.16 Mixed Occupancies
1301.6.16 Performance Compliance Methods, Mixed Occupancies
Where a building has two or more occupancies that are not in the same occupancy classification, the separation between the mixed occupancies shall ...
Existing Building Code 2021 of Illinois > 13 Performance Compliance Methods > 1301 General > 1301.6 Evaluation Process > 1301.6.16 Mixed Occupancies
(A) Special Occupancies, Group IIC
B, as described in 500.6(A)(1) and (A)(2) ...
National Electrical Code 2017 of Illinois > 5 Special Occupancies > 505 Zone 0, 1, and 2 Locations > 505.6 Material Groups > (A) Group IIC