722.5.2.2.1 Minimum Thickness
JUMP TO FULL CODE CHAPTER
The use of Equation 7-17 is subject to the following conditions:
- The weight-to-heated-perimeter ratio for the substitute beam or girder (W2/D2) shall be not less than 0.37.
- The thickness of fire protection materials calculated for the substitute beam or girder (T1) shall be not less than 3/8 inch (9.5 mm).
- The unrestrained or restrained beam rating shall be not less than 1 hour.
- Where used to adjust the material thickness for a restrained beam, the use of this procedure is limited to structural steel sections classified as compact in accordance with AISC 360.
Related Code Sections
2514.2 Gypsum Board, Gypsum Panel Products and Plaster, Minimum Thickness
The minimum thickness of reinforced gypsum concrete shall be 2 inches (51 mm) except the minimum required thickness shall be reduced to 1 1 / 2 ...
Building Code 2021 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2514 Reinforced Gypsum Concrete > 2514.2 Minimum Thickness
2514.2 Gypsum Board, Gypsum Panel Products and Plaster, Minimum Thickness
The minimum thickness of reinforced gypsum concrete shall be 2 inches (51 mm) except the minimum required thickness shall be reduced to 1 1 / 2 ...
Building Code 2018 of Illinois > 25 Gypsum Board, Gypsum Panel Products and Plaster > 2514 Reinforced Gypsum Concrete > 2514.2 Minimum Thickness
722.5.2.2.1 Fire and Smoke Protection Features, Minimum Thickness
2 ) shall be not less than 0.37. The thickness of fire protection materials calculated for the substitute beam or girder (T 1 ) shall ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.5 Steel Assemblies > 722.5.2 Structural Steel Beams and Girders > 722.5.2.2 Sprayed Fire-Resistant Materials > 722.5.2.2.1 Minimum Thickness
722.5.2.2.1 Fire and Smoke Protection Features, Minimum Thickness
) shall be not less than 0.37. The thickness of fire protection materials calculated for the substitute beam or girder (T 1 ) shall be not less ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.5 Steel Assemblies > 722.5.2 Structural Steel Beams and Girders > 722.5.2.2 Sprayed Fire-Resistant Materials > 722.5.2.2.1 Minimum Thickness
18.12.6 Earthquake-Resistant Structures, Minimum Thickness of Diaphragms
Concrete slabs and composite topping slabs serving as diaphragms used to transmit earthquake forces shall be at least 2 in. thick. Topping slabs ...
Building Code Requirements for Structural Concrete of Illinois > 18 Earthquake-Resistant Structures > 18.12 Diaphragms and Trusses > 18.12.6 Minimum Thickness of Diaphragms