406.4.1 Minimum Standards for Nonmercury Gauges
JUMP TO FULL CODE CHAPTER
- This section establishes minimum standards for nonmercury gauges to test gas piping, drainage and vent systems.
- Each gauge shall meet the following requirements:
- The gauge shall be manufactured and used in accordance with ASME B40.100, which incorporates ASME B40.1 and ASME B40.7, and the manufacturer shall provide with the gauge a written statement that the gauge is manufactured in accordance with such ASME standard;
- The gauge shall be labeled with the name of the manufacturer;
- The gauge shall be kept in a padded separate rigid box and the manufacturer's instructions for use and protection of the gauge shall be complied with;
- The units of measurement "psig" shall appear on the face of the gauge; and
- The gauge shall be kept in good working order.
Related Code Sections
406.4.1 Gas Piping Installations, Minimum Standards for Nonmercury Gauges
This section establishes minimum standards for nonmercury gauges to test gas piping, drainage and vent systems.
Each gauge shall meet ...
NYC Fuel Gas Code 2014 > 4 Gas Piping Installations > 406 Inspection, Testing and Purging > 406.4 Test Pressure Measurement > 406.4.1 Minimum Standards for Nonmercury Gauges
406.4.3 Gas Piping Installations, Minimum Standards for Gauges
This section establishes minimum standards for gauges used to test gas
piping.
Each gauge shall meet the following requirements:
The gauge ...
NYC Fuel Gas Code 2022 > 4 Gas Piping Installations > 406 Inspection, Testing and Purging > 406.4 Test Pressure Measurement > 406.4.3 Minimum Standards for Gauges
406.4.1 Gas Piping Installations, Minimum Standards for Non-Mercury Gauges:
1. This section establishes minimum standards for non-mercury gauges to test gas piping, drainage and vent systems. 2. Each ...
NYC Fuel Gas Code 2008 > 4 Gas Piping Installations > 406 Inspection, Testing and Purging > 406.4 Test Pressure Measurement > 406.4.1 Minimum Standards for Non-Mercury Gauges:
Appendix A Selected Rules of the Department of Buildings [PDF] (page 67)
for the year 2001, the rules in this section establish minimum standards for non-mercury gauges to test gas piping, drainage and vent systems. (b) Minimum ...
Section 1010 Boilers, Water Heaters and Pressure Vessels, Gauges
Every hot water boiler shall have a pressure gauge and a temperature gauge, or a combination pressure and temperature gauge. The gauges shall ...