301.4.1 Minimum Rehabilitated Landscape Area Requirement for Existing Sites
JUMP TO FULL CODE CHAPTER
[DSA-SS] A minimum rehabilitated landscape area equal to 75 percent of the footprint area of a new building or of an addition to an existing building shall be provided and comply with Section 5.304.6.
Exceptions:
- The new building or addition to an existing building is less than 1,600 square feet in floor area.
- The entire existing site's irrigated landscape areas are in full compliance with Section 5.304.6.
- The new building or addition to an existing building is to be partially or entirely constructed on an existing irrigated landscape or turf lawn area which is not in compliance with the current MWELO requirements and is equal to or greater than the minimum rehabilitated landscape area requirement of Section 301.4.1.
Related Code Sections
301.4.1 Green Building, Minimum Rehabilitated Landscape Area Requirement for Existing Sites
[DSA-SS] A minimum rehabilitated landscape area equal to 75 percent of the footprint area of a new building or of an addition to an existing ...
California Green Building Standards Code 2016 > 3 Green Building > 301 General > 301.4 Public Schools and Community Colleges > 301.4.1 Minimum Rehabilitated Landscape Area Requirement for Existing Sites
301.4 Green Building, Mandatory Measures for Public Schools and Community Colleges
A minimum rehabilitated landscape area equal to 75 percent ...
California Green Building Standards Code 2019 > 3 Green Building > 301 General > 301.4 Mandatory Measures for Public Schools and Community Colleges
5.304.6.2 Nonresidential Mandatory Measures, Rehabilitated Landscapes
Rehabilitated landscape projects with an aggregate landscape area equal to or greater than 1,200 square feet ...
California Green Building Standards Code 2019 > 5 Nonresidential Mandatory Measures > 5.304 Outdoor Water Use > 5.304.6 Outdoor Potable Water Use in Landscape Areas > 5.304.6.2 Rehabilitated Landscapes
5.304.6.2 Nonresidential Mandatory Measures, Rehabilitated Landscapes
[DSA-SS] Rehabilitated landscape projects with an aggregate landscape area equal to or greater than 1,200 square feet ...
California Green Building Standards Code 2016 > 5 Nonresidential Mandatory Measures > 5.304 Outdoor Water Use > 5.304.6 Outdoor Potable Water Use in Landscape Areas [DSA-SS] > 5.304.6.2 Rehabilitated Landscapes
5.106.12.2 Nonresidential Mandatory Measures, Landscape Areas
Shade tree plantings, minimum No. 10 container size or equal shall be installed to provide shade of 20% of the landscape area within 15 years ...
California Green Building Standards Code 2019 > 5 Nonresidential Mandatory Measures > 5.106 Site Development > 5.106.12 Shade Trees > 5.106.12.2 Landscape Areas