// CODE SNIPPET
1305.2 Minimum Flow Rates
JUMP TO FULL CODE CHAPTER
Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2.
TABLE 1305.2
MINIMUM FLOW RATES (cubic feet per minute)
MINIMUM FLOW RATES (cubic feet per minute)
MEDICAL SYSTEM | FLOW RATE |
---|---|
Oxygen | .71 CFM per outlet1 |
Nitrous Oxide | .71 CFM per outlet1 |
Medical Compressed Air | .71 CFM per outlet1 |
Nitrogen | 15 CFM free air per outlet |
Vacuum | 1 SCFM per inlet2 |
Carbon Dioxide | .71 CFM per outlet1 |
Helium | .71 CFM per outlet |
For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s
Notes:
1 A room designed for a permanently located respiratory ventilator or anesthesia machine shall have an outlet capable of a flow rate of 6.36 CFM (3.0 L/s) at the station outlet.
2 For testing and certification purposes, individual station inlets shall be capable of a flow rate of 3 SCFM (1.4 L/s), while maintaining a system pressure of not less than 12 inches of mercury (41 kPa) at the nearest adjacent vacuum inlet.
Related Code Sections
1305.2 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Minimum Flow Rates
Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2. TABLE 1305.2 MINIMUM FLOW RATES (cubic feet per ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1305.0 System Performance > 1305.2 Minimum Flow Rates
20.5.6.5 Special Designs of Storage Protection,
For multiple-level catwalk systems, a minimum of 10 sprinklers, five on each of the top two levels, shall be calculated with a minimum flow rate ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 20 Special Designs of Storage Protection > 20.5 Sprinkler Protection of Carton Records Storage With Catwalk Access > 20.5.6 Sprinkler Criteria > 20.5.6.5
25.2.5.2 Systems Acceptance,
The minimum flow rate shall be the system demand, including hose stream allowance where applicable ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 25 Systems Acceptance > 25.2 Acceptance Requirements > 25.2.5 Backflow Prevention Assemblies > 25.2.5.2
10.10.2.5.2 Underground Requirements,
The minimum flow rate required by 10.10.2.5.1 shall be the system demand, including hose stream demand where applicable. [ 24: 10.10.2.5.2] ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 10 Underground Requirements > 10.10 Testing and Acceptance > 10.10.2 Acceptance Requirements > 10.10.2.5 Backflow Prevention Assemblies > 10.10.2.5.2
8.17.4.5.1* Installation Requirements, Backflow Prevention Valves
Means shall be provided downstream of all backflow prevention valves for forward flow tests at a minimum flow rate of the system demand including ...
Standard for the Installation of Sprinkler Systems 2016 of Nevada > 8 Installation Requirements > 8.17 System Attachments > 8.17.4 System Connections > 8.17.4.5* Backflow Devices > 8.17.4.5.1* Backflow Prevention Valves