403.7.2.2 Minimum Exhaust Rate
Go To Full Code Chapter
[HCD 1 & 2] In lieu of the exhaust rates in Table 403.7, ventilation
systems shall be capable of providing 14,000
cfm (6608 L/s) of exhaust air for each operating
vehicle. Number of operating vehicles shall be determined
based on 2.5 percent of all parking spaces
(and not less than one vehicle).