1808.2.13 Minimum Concrete Cover
JUMP TO FULL CODE CHAPTER
The minimum concrete cover for cast-in-place and precast concrete piles shall be as shown in Table 1808.2.13.
TABLE 1808.2.13 MINIMUM CONCRETE COVER FOR CAST IN PLACE AND PRECAST CONCRETE PILESa
TABLE 1808.2.13 MINIMUM CONCRETE COVER FOR CAST IN PLACE AND PRECAST CONCRETE PILESa
FOUNDATION ELEMENT OR CONDITION | MINIMUM COVER |
1. Precast nonprestressed deep foundation elements | |
Exposed to seawater | 3 inches |
Not manufactured under plant conditions | 2 inches |
Manufactured under plant control conditions | In accordance with Section 7.7.3 of ACI 318 |
2. Precast prestressed deep foundation elements | |
Exposed to seawater | 2.5 inches |
Other | In accordance with Section 7.7.3 of ACI 318 |
3. Cast-in-place deep foundation elements not enclosed by a steel pipe, tube or permanent casing | 2.5 inches |
4. Cast-in-place deep foundation elements enclosed by a steel pipe, tube or permanent casing | 1 inch |
5. Structural steel core within a steel pipe, tube or permanent casing | 2 inches |
6. Cast-in-place drilled shafts enclosed by a stable rock socket | 1.5 inches |
For SI: 1 inch = 25.4 mm. |
a. The concrete cover provided for prestressed and nonprestressed reinforcement in foundations shall be no less than the largest applicable value specified in Table 1808.2.13. Longitudinal bars spaced less than 11/2 inches (38 mm) clear distance apart shall be considered bundled bars for which the concrete cover provided shall also be no less than that required by Section 7.7.4 of ACI 318. Concrete cover shall be measured from the concrete surface to the outermost surface of the steel to which the cover requirement applies. Where concrete is placed in a temporary or permanent casing or a mandrel, the inside face of the casing or mandrel shall be considered the concrete surface. |
Related Code Sections
1808.2.13 Soils and Foundations, Minimum Concrete Cover
The minimum concrete cover for cast-in-place and precast concrete piles shall be as shown in Table 1808.2.13. TABLE 1808.2.13 MINIMUM CONCRETE ...
NYC Building Code 2014 > 18 Soils and Foundations > 1808 Deep Foundations > 1808.2 Piles—General Requirements > 1808.2.13 Minimum Concrete Cover
721.5.1.4.3 Fire and Smoke Protection Features, Minimum Concrete Cover
the thickness of concrete cover required for various fire-resistance ratings for typical wide-flange sections. The thicknesses of concrete indicated ...
NYC Building Code 2014 > 7 Fire and Smoke Protection Features > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.4 Concrete-Protected Columns > 721.5.1.4.3 Minimum Concrete Cover
721.5.1.4.3 Fire-Resistance-Rated Construction, Minimum Concrete Cover
the thickness of concrete cover required for various fire-resistance ratings for typical wide-flange sections. The thicknesses of concrete indicated ...
NYC Building Code 2008 > 7 Fire-Resistance-Rated Construction > 721 Calculated Fire Resistance > 721.5 Steel Assemblies > 721.5.1 Structural Steel Columns > 721.5.1.4 Concrete-Protected Columns > 721.5.1.4.3 Minimum Concrete Cover
1907.7 Concrete, Concrete Protection for Reinforcement
The minimum concrete cover for reinforcement shall comply with Sections 1907.7.1 through 1907.7.7 ...
NYC Building Code 2008 > 19 Concrete > 1907 Details of Reinforcement > 1907.7 Concrete Protection for Reinforcement
1907.7 Concrete, Concrete Protection for Reinforcement
The minimum concrete cover for reinforcement shall comply with Sections 1907.7.1 through 1907.7.8 ...
NYC Building Code 2014 > 19 Concrete > 1907 Details of Reinforcement > 1907.7 Concrete Protection for Reinforcement