17.2.4.7.1 Minimum Coach Screw Rod Size
Go To Full Code Chapter
The size of coach screw rods shall not be less than the requirements of Table 17.2.4.7.1.
Table 17.2.4.7.1 Minimum Coach Screw Rod Size
Pipe Size | Diameter of Rod | Minimum Penetration | |||
---|---|---|---|---|---|
in. | mm | in. | mm | in. | mm |
Up to and including 4 | 100 | 3/8 | 10 | 3 | 75 |
Larger than 4 | 100 | NP | NP | NP | NP |
NP: Not permitted.