3.4.2 Minimum Bottom and Top Car Runby
Go To Full Code Chapter
3.4.2.1 Bottom Car Runby
The bottom car runby shall be
(a) not less than 75 mm (3 in.) for operating speed(s) in the down direction up to 0.50 m/s (100 ft/min)
(b) increased from 75 mm (3 in.) to 150 mm (6 in.) in proportion to the increase in operating speed(s) in the down direction from 0.50 m/s (100 ft/min) to 1 m/s (200 ft/min)
(c) aminimum 150 mm (6 in.) for operating speed(s) in the down direction exceeding 1 m/s (200 ft/min)
3.4.2.2 Car Top Minimum Runby
The top runby of the car shall be
(a) not less than 75 mm (3 in.) for rated speeds up to 0.50 m/s (100 ft/min)
(b) increased from 75 mm (3 in.) to 150 mm (6 in.) in proportion to the increase in rated speed from 0.50 m/s (100 ft/min) to 1 m/s (200 ft/min)
(c) a minimum 150 mm (6 in.) for rated speeds exceeding 1 m/s (200 ft/min)
Related Code Sections
3.4.2 Hydraulic Elevators, Minimum Bottom and Top Car Runby
The bottom car runby shall be (a) not less than 75 mm (3 in.) for operating speed(s) in the down direction up to 0.50 m/s (100 ft/min) (b ...
4.2.2.2 Elevators With Other Types of Driving Machines, Minimum and Maximum Bottom and Top Car Runby
The minimum bottom and top car runby shall be not less than (a) 75 mm (3 in.) for rated speeds not exceeding 0.5 m/s (100 ft/min) (b) 150 mm (6 ...
7.4.6 Dumbwaiters and Material Lifts, Vertical Clearances and Runbys for Cars and Counterweights
lifts, bottom and top car clearances and runbys for cars and counterweights shall conform to 7.4.6.1.1 through 7.4.6.1.4 ...
7.4.6.2 Dumbwaiters and Material Lifts,
For Type B material lifts, bottom and top car clearances and runbys for cars and counterweights shall conform to 7.4.6.2.1 through 7.4.6.2.3 ...
Section 3.4 Hydraulic Elevators, Bottom and Top Clearances and Runbys for Cars and Counterweights
) Neither the top nor the bottom runby of the car shall ...