Section 3510 Microturbines
JUMP TO FULL CODE CHAPTER
This section shall govern the design, installation, operation and maintenance of microturbines when the aggregate electrical energy produced by all microturbines on or within a single building, including building roofs and setbacks, does not exceed 2,000 kW.
The operation of a microturbine during regular business hours shall be under the personal supervision of a certificate of fitness holder. At all other times, a microturbine shall be under the general supervision of a certificate of fitness holder. Certificate of fitness holders shall be trained by the manufacturer or other qualified and knowledgeable person in the safe operation of the equipment, including how to safely shut down the equipment in the event of an emergency.
The alarms initiated from the operation of a microturbine shall be annunciated both locally and remotely as required by the construction codes, including the Building Code and Mechanical Code, and the Electrical Code. The remote panel shall be located in a continuously supervised location on the premises.
Microturbines shall be designed and installed in accordance with the construction codes, including the Building Code and the Mechanical Code, and the Electrical Code. A copy of the design and installation documents for microturbine installations approved by the Department of Buildings shall be submitted to the department prior to installation.
Facilities housing microturbines shall be operated and maintained in compliance with the requirements of FC 3510.5.1 through 3510.5.4.
Signage and diagrams shall be provided in compliance with the requirements of FC 3510.5.1.1 through 3510.5.1.3.
The fail safe emergency natural gas shutoff valve shall have a durable sign conspicuously posted near such valve that reads: "MICROTURBINE EMERGENCY GAS SHUTOFF."
A durable diagram shall be conspicuously posted on all doors and other entrances to a microturbine room or area indicating the location of all manual and automatic natural gas shutoff valves.
A durable sign shall be conspicuously posted on or near each door or other entrance to a room or outdoor area in which a microturbine is located, and on or adjacent to the microturbine itself, that reads "HIGH PRESSURE NATURAL GAS."
The microturbine shall be located in an area protected from unauthorized entry. Doors to rooms containing a microturbine shall be kept locked, but a key to such locks shall be readily available on the premises to certificate of fitness holders, maintenance personnel, and emergency responders.
Combustible material shall not be stored and combustible waste shall not be allowed to accumulate in rooms or within 10 feet (3048 mm) of outdoor areas in which microturbines are located.
The owner of any microturbine installation shall maintain a service contract with the microturbine manufacturer or other qualified service company as long as the installation exists on the premises. A copy of the service contract shall be maintained on the premises and made available for inspection by any department representative.
Related Code Sections
Appendix A Selected Rules of the Department of Buildings [PDF] (page 134)
Rules and Regulations (5) Installation. (i) Regulation. Installation of microturbine systems shall be in accordance with all applicable requirements ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 135)
Rules and Regulations (ii) Enclosure. All microturbine system components shall be contained within integral weather-proof enclosures pursuant ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 133)
Requirements for the Installation of HighPressure Natural Gas-Fired Microturbine Systems (a) General requirements. All microturbine systems shall comply ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 136)
Rules and Regulations mechanical equipment room in accordance with the microturbine manufacturer’s recommendations, at a rate adequate to dilute ...
Appendix A Selected Rules of the Department of Buildings [PDF] (page 6)
Gas-Fired Microturbine Systems Ch. 51 Dormitories §51-01 Classification of Student Dormitory Ch. 52 Notification to the Department of Commencement ...