1810.3.10 Micropiles
JUMP TO FULL CODE CHAPTER
Micropiles shall be designed and detailed in accordance with Sections 1810.3.10.1 through 1810.3.10.4.
Micropiles shall develop their load-carrying capacity by means of a bond zone in soil, bedrock or a combination of soil and bedrock. Micropiles shall be grouted and have either a steel pipe or tube or steel reinforcement at every section along the length. It shall be permitted to transition from deformed reinforcing bars to steel pipe or tube reinforcement by extending the bars into the pipe or tube section by not less than their development length in tension in accordance with ACI 318.
Reinforcement shall consist of deformed reinforcing bars in accordance with ASTM A615 Grade 60 or 75 or ASTM A722 Grade 150.
The steel pipe or tube shall have a minimum wall thickness of 3/16 inch (4.8 mm). Splices shall comply with Section 1810.3.6. The steel pipe or tube shall have a minimum yield strength of 45,000 psi (310 MPa) and a minimum elongation of 15 percent as shown by mill certifications or two coupon test samples per 40,000 pounds (18 160 kg) of pipe or tube.
For micropiles or portions thereof grouted inside a temporary or permanent casing or inside a hole drilled into bedrock or a hole drilled with grout, the steel pipe or tube or steel reinforcement shall be designed to carry not less than 40 percent of the design compression load. Micropiles or portions thereof grouted in an open hole in soil without temporary or permanent casing and without suitable means of verifying the hole diameter during grouting shall be designed to carry the entire compression load in the reinforcing steel. Where a steel pipe or tube is used for reinforcement, the portion of the grout enclosed within the pipe is permitted to be included in the determination of the allowable stress in the grout.
For structures assigned to Seismic Design Category C, a permanent steel casing shall be provided from the top of the micropile down to the point of zero curvature. For structures assigned to Seismic Design Category D, E or F, the micropile shall be considered as an alternative system in accordance with Section 104.11. The alternative system design, supporting documentation and test data shall be submitted to the building official for review and approval.
Related Code Sections
1810.3.10 Soils and Foundations, Micropiles
Micropiles shall be designed and detailed in accordance with Sections 1810.3.10.1 through 1810.3.10.4 ...
Building Code 2021 of Illinois > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.10 Micropiles
1810.3.10 Soils and Foundations, Micropiles
Micropiles shall be designed and detailed in accordance with Sections 1810.3.10.1 through 1810.3.10.4 ...
Building Code 2018 of Illinois > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.10 Micropiles
1810.3.10.4 Soils and Foundations, Seismic Reinforcement
For structures assigned to Seismic Design Category C, a permanent steel casing shall be provided from the top of the micropile down to the point ...
Building Code 2018 of Illinois > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.10 Micropiles > 1810.3.10.4 Seismic Reinforcement
1810.3.10.1 Soils and Foundations, Construction
Micropiles shall develop their load-carrying capacity by means of a bond zone in soil, bedrock or a combination of soil and bedrock. Micropiles shall ...
Building Code 2021 of Illinois > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.10 Micropiles > 1810.3.10.1 Construction
1810.3.10.1 Soils and Foundations, Construction
Micropiles shall develop their load-carrying capacity by means of a bond zone in soil, bedrock or a combination of soil and bedrock. Micropiles shall ...
Building Code 2018 of Illinois > 18 Soils and Foundations > 1810 Deep Foundations > 1810.3 Design and Detailing > 1810.3.10 Micropiles > 1810.3.10.1 Construction