M 102.3 Meter and Building Supply
JUMP TO FULL CODE CHAPTER
To determine the design flow rate for the water meter and building supply, enter the total number of indoor plumbing fixtures and appliances for the building in Column [B] of the Water Demand Calculator and run Calculator. See Table M 102.3 for an example.
TABLE M 102.3
WATER DEMAND CALCULATOR EXAMPLE
WATER DEMAND CALCULATOR EXAMPLE
[A] FIXTURE | [B] ENTER NUMBER OF FIXTURES | [C] PROBABILITY OF USE (%) | [D] ENTER FIXTURE FLOW RATE (GPM) | [E] MAXIMUM RECOMMENDED FIXTURE FLOW RATE (GPM) | |
---|---|---|---|---|---|
1 | Bar Sink | 0 | 2.0 | 1.5 | 1.5 |
2 | Bathtub | 0 | 1.0 | 5.5 | 5.5 |
3 | Bidet | 0 | 1.0 | 2.0 | 2.0 |
4 | Clothes Washer | 1 | 5.5 | 3.5 | 3.5 |
5 | Combination Bath/Shower | 1 | 5.5 | 5.5 | 5.5 |
6 | Dishwasher | 1 | 0.5 | 1.3 | 1.3 |
7 | Kitchen Faucet | 1 | 2.0 | 2.2 | 2.2 |
8 | Laundry Faucet | 0 | 2.0 | 2.0 | 2.0 |
9 | Lavatory Faucet | 1 | 2.0 | 1.5 | 1.5 |
10 | Shower, per head | 0 | 4.5 | 2.0 | 2.0 |
11 | Water Closet, 1.28 GPF Gravity Tank | 1 | 1.0 | 3.0 | 3.0 |
12 | Other Fixture 1 | 0 | 0.0 | 0.0 | 6.0 |
13 | Other Fixture 2 | 0 | 0.0 | 0.0 | 6.0 |
14 | Other Fixture 3 | 0 | 0.0 | 0.0 | 6.0 |
Total Number of Fixtures | 6 | RESET | RUN WATER DEMAND CALCULATOR | ||
99th Percentile Demand Flow = | 8.5 GPM |
Related Code Sections
M 102.3 Peak Water Demand Calculator, Meter and Building Supply
To determine the design flow rate for the water meter and building supply, enter the total number of indoor plumbing fixtures and appliances ...
Uniform Plumbing Code 2018 of Nevada > M Peak Water Demand Calculator > M 102.0 Demand Load > M 102.3 Meter and Building Supply
610.8 Water Supply and Distribution, Size of Meter and Building Supply Pipe Using Table 610.4
The size of the meter and the building supply pipe shall be determined as follows:
Determine the available pressure at the water meter or other ...
Uniform Plumbing Code 2018 of Nevada > 6 Water Supply and Distribution > 610.0 Size of Potable Water Piping > 610.8 Size of Meter and Building Supply Pipe Using Table 610.4
L 407.0 Sustainable Practices, Meters
A water meter shall be required for buildings connected to a public water system, including municipally supplied reclaimed (recycled) water. In other ...
A 102.2 Recommended Rules for Sizing the Water Supply System, Water Meter
Where the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow of meters in the range of sizes ...
Uniform Plumbing Code 2018 of Nevada > A Recommended Rules for Sizing the Water Supply System > A 102.0 Preliminary Information > A 102.2 Water Meter