603.4 Metallic Ducts

Mechanical Code 2015 of Utah > 6 Duct Systems > 603 Duct Construction and Installation > 603.4 Metallic Ducts
JUMP TO FULL CODE CHAPTER
Metallic ducts shall be constructed as specified in the SMACNA HVAC Duct Construction Standards‒Metal and Flexible.

Exception: Ducts installed within single dwelling units shall have a minimum thickness as specified in Table 603.4.


TABLE 603.4 DUCT CONSTRUCTION MINIMUM SHEET METAL THICKNESS FOR SINGLE DWELLING UNITSa

ROUND DUCT DIAMETER
(inches)
STATIC PRESSURE
1/2-inch water gage 1-inch water gage
Thickness (inches) Thickness (inches)
Galvanized Aluminum Galvanized Aluminum
<12 0.013 0.018 0.013 0.018
12 to14 0.013 0.018 0.016 0.023
15 to 17 0.016 0.023 0.019 0.027
18 0.016 0.023 0.024 0.034
19 to 20 0.019 0.027 0.024 0.034
RECTANGULAR DUCT DIMENSION
(inches)
STATIC PRESSURE
1/2-inch water gage 1-inch water gage
Thickness (inches) Thickness (inches)
Galvanized Aluminum Galvanized Aluminum
8 0.013 0.018 0.013 0.018
9 to 10 0.013 0.018 0.016 0.023
11 to 12 0.016 0.023 0.019 0.027
13 to 16 0.019 0.027 0.019 0.027
17 to 18 0.019 0.027 0.024 0.034
19 to 20 0.024 0.034 0.024 0.034

For SI: 1 inch = 25.4 mm, 1-inch water gage = 249 Pa.
  1. Ductwork that exceeds 20 inches by dimension or exceeds a pressure of 1-inch water gage shall be constructed in accordance with SMACNA HVAC Duct Construction Standards‒Metal and Flexible.

603.4.1 Minimum Fasteners

Round metallic ducts shall be mechanically fastened by means of not less than three sheet metal screws or rivets spaced equally around the joint.

Exception: Where a duct connection is made that is partially inaccessible, three screws or rivets shall be equally spaced on the exposed portion so as to prevent a hinge effect.

603.4.2 Duct Lap

Crimp joints for round and oval metal ducts shall be lapped not less than 1 inch (25 mm) and the male end of the duct shall extend into the adjoining duct in the direction of airflow.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


603.4 Duct Systems, Metallic ducts
Metallic ducts shall be constructed as specified in the SMACNA HVAC Duct Construction Standards—Metal and Flexible . Exception: Ducts installed ...
Mechanical Code 2018 of Utah > 6 Duct Systems > 603 Duct Construction and Installation > 603.4 Metallic ducts
603.4 Duct Systems, Metallic Ducts
Metallic ducts shall be constructed as specified in the SMACNA HVAC Duct Construction Standards‒Metal and Flexible . Exception: Ducts ...
Mechanical Code 2015 of Utah > 6 Duct Systems > 603 Duct Construction and Installation > 603.4 Metallic Ducts
M1601.1.2 Duct Systems, Underground Duct Systems
Underground duct systems shall be constructed of approved concrete, clay, metal or plastic. The maximum duct temperature for plastic ducts shall ...
Residential Code 2015 of Utah > 16 Duct Systems > M1601 Duct Construction > M1601.1 Duct Design > M1601.1.2 Underground Duct Systems
M1601.2 Duct Systems, Vibration Isolators
Vibration isolators installed between mechanical equipment and metal ducts shall be fabricated from approved materials and shall not exceed 10 ...
Residential Code 2015 of Utah > 16 Duct Systems > M1601 Duct Construction > M1601.2 Vibration Isolators
M1601.4 Duct Systems, Installation
Factory-made air ducts shall not be installed in or on the ground, in tile or metal pipe, or within masonry or concrete ...
Residential Code 2015 of Utah > 16 Duct Systems > M1601 Duct Construction > M1601.4 Installation
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US