E3609.6 Metal Water Piping Bonding
JUMP TO FULL CODE CHAPTER
The metal water piping system shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or more grounding electrodes used. The bonding jumper shall be sized in accordance with Table E3603.1. The points of attachment of the bonding jumper(s) shall be accessible.
Related Code Sections
E3609.6 Services, Metal Water Piping Bonding
The metal water piping system shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode ...
E3609.6 Services, Metal Water Piping Bonding
The metal water piping system shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode ...
E3608.1.1 Services, Metal Underground Water Pipe
A metal underground water pipe that is in direct contact with the earth for 10 feet (3048 mm) or more, including any well casing effectively bonded ...
2012 Virginia Residential Code > 36 Services > E3608 Grounding Electrode System > E3608.1 Grounding Electrode System > E3608.1.1 Metal Underground Water Pipe
E3608.1.1 Services, Metal Underground Water Pipe
A metal underground water pipe that is in direct contact with the earth for 10 feet (3048 mm) or more, including any well casing effectively bonded ...
2015 Virginia Residential Code > 36 Services > E3608 Grounding Electrode System > E3608.1 Grounding Electrode System > E3608.1.1 Metal Underground Water Pipe
E3611.4 Services, Interior Metal Water Piping
Where grounding electrode conductors and bonding jumpers are connected to interior metal water piping as a means to extend the grounding electrode ...
2012 Virginia Residential Code > 36 Services > E3611 Grounding Electrode Conductor Connection to the Grounding Electrodes > E3611.4 Interior Metal Water Piping