// CODE SNIPPET
508.5.1.4 Medium-Duty Cooking Appliances
JUMP TO FULL CODE CHAPTER
The minimum net airflow for hoods used for cooking
appliances such as electric and gas hot-top
ranges, gas open-burner ranges (with or without
oven), electric and gas flat griddles, electric and gas
double-sided griddles, electric and gas fryers
(including open deep fat fryers, donut fryers, kettle
fryers, and pressure fryers), and electric and gas conveyor
pizza ovens shall be in accordance with Table
508.5.1.4.
For SI units: 1 cubic foot per minute = 0.00047 m3/s, 1 foot = 304.8 mm
TYPE OF HOOD | AIRFLOW (cubic foot per minute per linear foot of hood) |
Backshelf/pass-over | 300 |
Double island canopy (per side) | 300 |
Eyebrow | 250 |
Single island canopy | 500 |
Wall-mounted canopy | 300 |
Related Code Sections
508.10.1.4 Exhaust Systems, Medium-Duty Cooking Appliances
MEDIUM-DUTY COOKING APPLIANCE AIRFLOW
TYPE OF HOOD
AIRFLOW (cubic foot per minute per linear foot of hood)
Backshelf ...
California Mechanical Code 2016 > 5 Exhaust Systems > 508.0 Hoods > 508.10 Hood Size > 508.10.1 Canopy Size and Location > 508.10.1.4 Medium-Duty Cooking Appliances
508.5.1.4 Exhaust Systems, Medium-Duty Cooking Appliances
508.5.1.4
MEDIUM-DUTY COOKING APPLIANCE AIRFLOW
TYPE OF HOOD
AIRFLOW (cubic foot per minute per linear foot of hood ...
California Mechanical Code 2019 > 5 Exhaust Systems > 508.0 Type I Hoods > 508.5 Hood Size > 508.5.1 Canopy Size and Location > 508.5.1.4 Medium-Duty Cooking Appliances
508.0 Exhaust Systems, Hoods
shall be in accordance with
Table 508.10.1.4.
TABLE 508.10.1.4 MEDIUM-DUTY COOKING APPLIANCE AIRFLOW
TYPE OF HOOD
AIRFLOW ...
508.10.1.3 Exhaust Systems, Heavy-Duty Cooking Appliances
The
minimum net airflow for hoods used for cooking
appliances such as gas under-fired broilers, gas chain
(conveyor) broilers, electric and gas wok ...
California Mechanical Code 2016 > 5 Exhaust Systems > 508.0 Hoods > 508.10 Hood Size > 508.10.1 Canopy Size and Location > 508.10.1.3 Heavy-Duty Cooking Appliances
508.10.1.5 Exhaust Systems, Light-Duty Cooking Appliances
, and electric and gas salamanders
shall be in accordance with Table 508.10.1.5.
TABLE 508.10.1.5
LlGHT-DUTY COOKING APPLIANCE AIRFLOW ...
California Mechanical Code 2016 > 5 Exhaust Systems > 508.0 Hoods > 508.10 Hood Size > 508.10.1 Canopy Size and Location > 508.10.1.5 Light-Duty Cooking Appliances