2.2-3.4.8.8 Medication Safety Zone and Storage
Go To Full Code Chapter
- A medication safety zone as described in Section 2.1-2.8.8 (Medication Safety Zones) shall be immediately accessible from pre- and post-procedure patient care areas.
- Provision shall be made for locked storage of medications.