• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

469.4.11.1 Medical Gas and Vacuum Standards

2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards
JUMP TO FULL CODE CHAPTER

469.4.11.1.1

If the functional program of the office surgery suite requires a medical gas system, it shall be a minimum a Level III piped medical gas system in accordance with NFPA 99. In lieu of a Level III piped oxygen system, anesthetizing equipment with a double yoke oxygen system is acceptable. If an anesthesia ventilator is planned to be used during the surgical procedure, then a Level III piped gas system shall be required.

469.4.11.1.2

As required by the functional program of the office surgery suite, either a piped clinical vacuum system in accordance with NFPA 99 or portable electrical vacuum equipment shall be provided. In either case, there shall be a redundant vacuum system or equipment exclusively dedicated to the anesthetizing equipment.

469.4.11.1.3

For piped systems, the number of station outlets shall meet the needs of the functional program. However, the minimum number of station outlets shall be as described in Table 469.4.11.1.3.
TABLE 469.4.11.1.3
MINIMUM STATION OUTLETS FOR PIPED GAS SYSTEMS IN OFFICE SURGERY SUITES
LOCATION OXYGEN VACUUM
Class A NA NA
Class B and C 2 2*
Post Operative Recovery 1 1
* An additional outlet shall be provided for anesthesia evacuation if necessary.

469.4.11.1.4

All piping, except control-line tubing, shall be identified. All valves shall be tagged, and a valve schedule shall be provided to the office surgery suite owner for permanent record and reference.

469.4.11.1.5

All gas cylinders in service and in storage shall be individually secured and located to prevent falling or being knocked over.

Related Code Sections


469.4.11.1 Special Detailed Requirements Based on Use and Occupancy, Medical Gas and Vacuum Standards
If the functional program of the office surgery suite requires a medical gas system, it shall be a minimum a Level III piped medical gas system ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards
469.4.11.1 Special Detailed Requirements Based on Occupancy and Use, Medical Gas and Vacuum Standards
If the functional program of the office surgery suite requires a medical gas system, it shall be a minimum a Level III piped medical gas system ...
2020 FBC - Building, 7th edition > 4 Special Detailed Requirements Based on Occupancy and Use > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards
469.4.11.1 Special Detailed Requirements Based on Use and Occupancy, Medical Gas and Vacuum Standards
If the functional program of the office surgery suite requires a medical gas system, it shall be a minimum of a Level III piped medical gas system ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards
469.4.11.1.2 Special Detailed Requirements Based on Use and Occupancy,
As required by the functional program of the office surgery suite, either a piped clinical vacuum system in accordance with NFPA 99 or portable ...
2014 FBC - Building, 5th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards > 469.4.11.1.2
469.4.11.1.3 Special Detailed Requirements Based on Use and Occupancy,
be as described in Table 2. TABLE 2 MINIMUM STATION OUTLETS FOR PIPED GAS SYSTEMS IN OFFICE SURGERY SUITES LOCATION OXYGEN VACUUM ...
2017 FBC - Building, 6th edition > 4 Special Detailed Requirements Based on Use and Occupancy > 469 Office Surgery Suite > 469.4 Physical Plant Standards > 469.4.11 Mechanical System Standards > 469.4.11.1 Medical Gas and Vacuum Standards > 469.4.11.1.3
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING