// CODE SNIPPET
1313.5.1 Medical Air Compressor Source
JUMP TO FULL CODE CHAPTER
The medical air compressors shall draw their air from a source of clean air. [NFPA 99:5.1.3.6.3.11(A)]
If an air source equal to or better than outside air (e.g., air already filtered for use in operating room ventilating systems) is available, it shall be permitted to be used for the medical air compressors with the following provisions:
- This alternate source of supply air shall be available on a continuous 24 hours-per-day, 7 days-per-week basis.
- Ventilating systems having fans with motors or drive belts located in the airstream shall not be used as a source of medical air intake. [NFPA 99:5.1.3.6.3.11(E)]
Related Code Sections
1313.5.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Medical Air Compressor Source
The medical air compressors shall draw their air from a source of clean air. [NFPA 99:5.1.3.6.3.11(A)]
If an air source equal to or better than ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1313.0 Medical Air Supply Systems > 1313.5 Air Sources > 1313.5.1 Medical Air Compressor Source
1314.1.3.1 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Category 1 and 2 Systems
The medical air compressors shall draw their air from a source of clean air. [NFPA 99:5.1.3.6.3.12(A)]
Where an air ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1314.0 Medical Air Systems > 1314.1 Medical Air Compressors > 1314.1.3 Air Sources > 1314.1.3.1 Category 1 and 2 Systems
1313.0 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Medical Air Supply Systems
compressor sources, or it shall be reconstituted from oxygen USP and oil-free, dry nitrogen NF.
It shall meet the requirements of medical air USP.
It ...
California Plumbing Code 2019 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1313.0 Medical Air Supply Systems
1314.0 Health Care Facilities and Medical Gas and Medical Vacuum Systems, Medical Air Systems
]
Air sources for medical air compressors shall comply with Section 1314.1.3.1 or
Section ...
California Plumbing Code 2016 > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1314.0 Medical Air Systems
215.0 Definitions, - M -
from cylinders, bulk containers, medical air
compressor sources, or be reconstituted from oxygen
USP and oil-free dry nitrogen NF.