N1103.6 (R403.6) Mechanical Ventilation (Mandatory)
JUMP TO FULL CODE CHAPTER
The building shall be provided with ventilation that complies with the requirements of Section M1505 or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
Fans used to provide whole-house mechanical ventilation shall meet the efficacy requirements of Table N1103.6.1.
Exception:
Where an air handler that is integral to tested and listed HVAC equipment is used to provide whole-house mechanical ventilation, the air handler shall be powered by an electronically commutated motor.
FAN LOCATION | AIR FLOW RATE MINIMUM (CFM) | MINIMUM EFFICACY (CFM/WATT) | AIR FLOW RATE MAXIMUM (CFM) |
HRV or ERV | Any | 1.2 cfm/watt | Any |
Range hoods | Any | 2.8 cfm/watt | Any |
In-line fan | Any | 2.8 cfm/watt | Any |
Bathroom, utility room | 10 | 1.4 cfm/watt | < 90 |
Bathroom, utility room | 90 | 2.8 cfm/watt | Any |
For SI: 1 cubic foot per minute = 28.3 L/min.
- When tested in accordance with HVI Standard 916.
Related Code Sections
N1103.6 [RE] Energy Efficiency, (R403.6) Mechanical Ventilation (Mandatory)
Fans used to provide whole-house mechanical ventilation shall meet ...
Residential Code 2018 of Kansas > 11 [RE] Energy Efficiency > N1103 (R403) Systems > N1103.6 (R403.6) Mechanical Ventilation (Mandatory)
R403.6 [RE] Residential Energy Efficiency, Mechanical Ventilation (Mandatory)
Mechanical Code , as applicable, or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers ...
Energy Conservation Code 2018 of Kansas > 4 [RE] Residential Energy Efficiency > R403 Systems > R403.6 Mechanical Ventilation (Mandatory)
C403.2.2 [CE] Commercial Energy Efficiency, Ventilation (Mandatory)
Ventilation, either natural or mechanical, shall be provided in accordance with Chapter 4 of the International Mechanical Code . Where mechanical ...
Energy Conservation Code 2018 of Kansas > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.2 System Design (Mandatory) > C403.2.2 Ventilation (Mandatory)
C403.7.6.2 [CE] Commercial Energy Efficiency, Ventilation Controls
Controls shall be provided on each HVAC system that are capable of and configured to automatically turn off the ventilation and exhaust fans within ...
Energy Conservation Code 2018 of Kansas > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.7 Ventilation and Exhaust Systems (Mandatory) > C403.7.6 Automatic Control of HVAC Systems Serving Guestrooms (Mandatory) > C403.7.6.2 Ventilation Controls
C403.8.3 [CE] Commercial Energy Efficiency, Fan Efficiency (Mandatory)
or energy performance. Powered wall/roof ventilators. Fans outside the scope of AMCA 205. Fans that are intended to operate only during emergency ...
Energy Conservation Code 2018 of Kansas > 4 [CE] Commercial Energy Efficiency > C403 Building Mechanical Systems > C403.8 Fans and Fan Controls > C403.8.3 Fan Efficiency (Mandatory)