Section 605 Mechanical Refrigeration
The following emergency devices or systems shall be periodically tested in accordance with the manufacturer's instructions and as required by the fire code official.
- Treatment and flaring systems.
- Valves and appurtenances necessary to the operation of emergency refrigeration control boxes.
- Fans and associated equipment intended to operate emergency ventilation systems.
- Detection and alarm systems.
A detector, or a sampling tube that draws air to a detector, shall be provided at an approved location where refrigerant from a leak is expected to accumulate. The system shall be designed to initiate audible and visible alarms inside of and outside each entrance to the refrigerating machinery room and transmit a signal to an approved location where the concentration of refrigerant detected exceeds the lesser of the following:
- The corresponding TLV-TWA values shown in the International Mechanical Code for the refrigerant classification.
- Twenty-five percent of the lower flammable limit (LFL).
Detection of a refrigerant concentration exceeding the upper detection limit or 25 percent of the lower flammable limit (LFL), whichever is lower, shall stop refrigerant equipment in the machinery room in accordance with Section 605.9.1.
Flammable and combustible materials shall not be stored in machinery rooms for refrigeration systems having a refrigerant circuit containing more than 220 pounds (100 kg) of Group A1 or 30 pounds (14 kg) of any other group refrigerant. Storage, use or handling of extra refrigerant or refrigerant oils shall be as required by Chapters 50, 53, 55 and 57.
Exception: This provision shall not apply to spare parts, tools and incidental materials necessary for the safe and proper operation and maintenance of the system.
Systems containing more than 6.6 pounds (3 kg) of ammonia refrigerant shall discharge vapor to the atmosphere in accordance with one of the following methods:
- Directly to atmosphere where the fire code official determines, on review of an engineering analysis prepared in accordance with Section 104.7.2, that a fire, health or environmental hazard would not result from atmospheric discharge of ammonia.
- Through an approved treatment system in accordance with Section 605.12.5.
- Through a flaring system in accordance with Section 605.12.6.
- Through an approved ammonia diffusion system in accordance with Section 605.12.7.
- By other approved means.
Exception: Ammonia/water absorption systems containing less than 22 pounds (10 kg) of ammonia and for which the ammonia circuit is located entirely outdoors.
Exhaust from mechanical ventilation systems serving refrigeration machinery rooms containing flammable, toxic or highly toxic refrigerants, other than ammonia, capable of exceeding 25 percent of the LFL or 50 percent of the IDLH shall be equipped with approved treatment systems to reduce the discharge concentrations to those values or lower.
Exception: Refrigeration systems containing Group A2L complying with Section 605.17.
Where refrigerant of Groups A2, A3, B2 and B3, as defined in the International Mechanical Code, are used, refrigeration machinery rooms shall conform to the Class I, Division 2 hazardous location classification requirements of NFPA 70.
Exceptions:
- Ammonia machinery rooms that are provided with ventilation in accordance with Section 1106.3 of the International Mechanical Code.
- Machinery rooms for systems containing Group A2L refrigerants that are provided with ventilation in accordance with Section 605.17.
Machinery rooms with systems containing Group A2L refrigerants shall comply with Sections 605.17.1 through 605.17.3.
Exception: Machinery rooms conforming to the Class 1, Division 2 hazardous location classification requirements of NFPA 70.
The machinery room shall be provided with a refrigerant detection system. The refrigerant detection system shall be in accordance with Section 605.8 and all of the following:
- The detectors shall activate at or below a refrigerant concentration of 25 percent of the LFL.
- Upon activation, the detection system shall activate the emergency ventilation system in Section 605.17.3.
- The detection, signaling and control circuits shall be supervised.
An emergency ventilation system shall be provided at the minimum exhaust rate specified in ASHRAE 15 or Table 605.17.2. Shut down of the emergency ventilation system shall be by manual means.
TABLE [M] 605.17.2
MINIMUM EXHAUST RATE
REFRIGERANT | Q (m3/sec) | Q (cfm) |
R32 | 15.4 | 32,600 |
R143a | 13.6 | 28,700 |
R444A | 6.46 | 13,700 |
R444B | 10.6 | 22,400 |
R445A | 7.83 | 16,600 |
R446A | 23.9 | 50,700 |
R447A | 23.8 | 50,400 |
R451A | 7.04 | 15,000 |
R451B | 7.05 | 15,000 |
R1234yf | 7.80 | 16,600 |
R1234ze(E) | 5.92 | 12,600 |