Wall and floor-ceiling assemblies that separate a mechanical equipment room or space from the remainder of the building shall have a sound transmission class (STC) of not less than 50 or an apparent sound transmission class (ASTC) of not less than 45 if the completed construction is field tested, Wall and floor-ceiling assemblies that separate a generator equipment room or space from the remainder of the building shall have a sound transmission class (STC) of not less than 60 or an apparent sound transmission class (ASTC) of not less than 55 if the completed construction is field tested.
Upcodes Diagrams

Related Code Sections

7.9.1.1* Means of Egress,
ventilation equipment. The standby generator shall be permitted to be used for the stair shaft and vestibule emergency lighting power supply ...
14.13.1.1* Means of Egress,
mechanical ventilation equipment. The standby generator shall be permitted to be used for the stair shaft and vestibule emergency lighting power supply ...
403.4 Special Detailed Requirements Based on Occupancy and Use, Emergency Systems
If the standby or emergency power system includes a generator set inside a building, the system shall be located in a separate room enclosed ...