M2301.2.12 Maximum Temperature Limitation
JUMP TO FULL CODE CHAPTER
Systems shall be equipped with means to limit the maximum water temperature of the system fluid entering or exchanging heat with any pressurized vessel inside the dwelling to 180°F (82°C). This protection is in addition to the required temperature- and pressure-relief valves required by Section M2301.2.3.
Related Code Sections
M2301.2.12 Solar Thermal Energy Systems, Maximum Temperature Limitation
Systems shall be equipped with means to limit the maximum water temperature of the system fluid entering or exchanging heat with any pressurized ...
2018 North Carolina Residential Code > 23 Solar Thermal Energy Systems > M2301 Thermal Solar Energy Systems > M2301.2 Design and Installation > M2301.2.12 Maximum Temperature Limitation
408.3 Fixtures, Faucets and Fixture Fittings, Bidet Water Temperature
The discharge water temperature from a bidet fitting shall be limited to a maximum temperature of 110°F (43°C) by a water temperature limiting device ...
2018 North Carolina Plumbing Code > 4 Fixtures, Faucets and Fixture Fittings > 408 Bidets > 408.3 Bidet Water Temperature
Section 408 Fixtures, Faucets and Fixture Fittings, Bidets
The discharge water temperature from a bidet fitting shall be limited to a maximum temperature of 110°F (43°C) by a water temperature ...
423.3 Fixtures, Faucets and Fixture Fittings, Footbaths, Pedicure Baths and Head Shampoo Sinks
be limited to a maximum temperature of 120°F (49°C) by a water temperature limiting device that conforms to ASSE 1070 or CSA B125.3 ...
2018 North Carolina Plumbing Code > 4 Fixtures, Faucets and Fixture Fittings > 423 Specialty Plumbing Fixtures > 423.3 Footbaths, Pedicure Baths and Head Shampoo Sinks