509.2.2 Maximum Input Rating
Go To Full Code Chapter
Where any or all of the appliances in Section 509.2.1(1) and Section 509.2.1(2) are installed so the aggregate input rating exceeds 20 (Btu/h)/ft3 (207 W/m3) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for conveying the vent gases to the outdoors so that the aggregate input rating of the remaining unvented appliances does not exceed 20 (Btu/h)/ft3 (207 W/m3). [NFPA 54:12.3.2.1]
Upcodes Diagrams
Related Code Sections
509.2.2 Water Heaters, Maximum Input Rating
Where any or all of the appliances in Section 509.2.1(1) and Section 509.2.1(2) are installed so the aggregate input rating exceeds 20 (Btu/h)/ft3 ...
G2428.1 Fuel Gas, (504.1) Definitions
maximum input rating of a Category I fan-assisted appliance attached to a vent or connector. NAT Max. The maximum input rating of a Category I draft-hood ...
G 101.7 Sizing of Venting Systems, Example 5(a): Common Venting a Draft Hood-Equipped Water Heater With a Fan-Assisted Furnace Into a Type B Vent
that a 3 inch (76 mm) vent connector has a maximum input rating of 37 000 Btu/h (10.8 kW). Although this rating is greater than the water heater input ...
(A) Special Conditions, Maximum Rated Current for a Specific Circuit
listing. Where the ESS has separate input (charge) and output (discharge) circuits or ratings, these shall be considered individually. Where the same ...
(A) Special Equipment, Calculation of Maximum Circuit Current
maximum input current shall be the stand-alone continuous inverter input current rating of the inverter producing rated power at the lowest input ...