// CODE SNIPPET
104-23 Maximum Floor Area Ratio for Commercial Uses
JUMP TO FULL CODE CHAPTER
In Subdistricts A and C, the maximum floor area ratio permitted for commercial uses shall be 6.0, except that the maximum floor area ratio for uses in Use Group 16 listed in Section 104-132 (Use Groups 16, 17 and 18) shall be 2.0.
Related Code Sections
2109.2.1.3 Masonry, Maximum Diaphragm Ratio
not exceed the values given in Table 2109.2.1.3.
TABLE 2109.2.1.3
DIAPHRAGM LENGTH-TO-WIDTH RATIOS
FLOOR OR ROOF DIAPHRAGM ...
NYC Building Code 2008 > 21 Masonry > 2109 Empirical Design of Masonry > 2109.2 Lateral Stability > 2109.2.1 Shear Walls > 2109.2.1.3 Maximum Diaphragm Ratio
904.11 Fire Protection Systems, Commercial Cooking Systems
at a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm) above the floor at its center. The manual actuation device shall require a maximum ...
NYC Building Code 2008 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.11 Commercial Cooking Systems
904.12 Fire Protection Systems, Commercial Cooking Systems
The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment ...
NYC Building Code 2022 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.12 Commercial Cooking Systems
904.11 Fire Protection Systems, Commercial Cooking Systems
) or less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation device shall require a maximum ...
NYC Building Code 2014 > 9 Fire Protection Systems > 904 Alternative Automatic Fire-Extinguishing Systems > 904.11 Commercial Cooking Systems
§27-566 Loads, Floor Live Loads
: members and connections (other than columns, piers, and walls) supporting floor areas used for storage (including warehouses, library stacks ...