710.1 Maximum Fixture Unit Load
JUMP TO FULL CODE CHAPTER
The maximum number of drainage fixture units connected to a given size of building sewer, building drain or horizontal branch of the building drain shall be determined using Table 710.1(1). The maximum number of drainage fixture units connected to a given size of horizontal branch or vertical soil or waste stack shall be determined using Table 710.1(2).
DIAMETER OF PIPE (inches) | MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS CONNECTED TO ANY PORTION OF THE BUILDING DRAIN OR THE BUILDING SEWER, INCLUDING BRANCHES OF THE BUILDING DRAINa | |||
Slope per foot | ||||
1/16 inch | 1/8 inch | 1/4 inch | 1/2 inch | |
11/4 | — | — | 1 | 1 |
11/2 | — | — | 3 | 3 |
2 | — | — | 21 | 26 |
21/2 | — | — | 24 | 31 |
3 | — | 36 | 42 | 50 |
4 | — | 180 | 216 | 250 |
5 | — | 390 | 480 | 575 |
6 | — | 700 | 840 | 1,000 |
8 | 1,400 | 1,600 | 1,920 | 2,300 |
10 | 2,500 | 2,900 | 3,500 | 4,200 |
12 | 3,900 | 4,600 | 5,600 | 6,700 |
15 | 7,000 | 8,300 | 10,000 | 12,000 |
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
- The minimum size of any building drain serving a water closet shall be 3 inches.
HORIZONTAL FIXTURE BRANCHES AND STACKSa
DIAMETER OF PIPE (inches) | MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS (dfu) | |||
Total for horizontal branch | Stacksb | |||
Total discharge into one branch interval | Total for stack of three branch Intervals or less | Total for stack greater than three branch intervals | ||
11/2 | 3 | 2 | 4 | 8 |
2 | 6 | 6 | 10 | 24 |
21/2 | 12 | 9 | 20 | 42 |
3 | 20 | 20 | 48 | 72 |
4 | 160 | 90 | 240 | 500 |
5 | 360 | 200 | 540 | 1,100 |
6 | 620 | 350 | 960 | 1,900 |
8 | 1,400 | 600 | 2,200 | 3,600 |
10 | 2,500 | 1,000 | 3,800 | 5,600 |
12 | 3,900 | 1,500 | 6,000 | 8,400 |
15 | 7,000 | Note c | Note c | Note c |
For SI: 1 inch = 25.4 mm.
- Does not include branches of the building drain. Refer to Table 710.1(1).
- Stacks shall be sized based on the total accumulated connected load at each story or branch interval. As the total accumulated connected load decreases, stacks are permitted to be reduced in size. Stack diameters shall not be reduced to less than one-half of the diameter of the largest stack size required.
- Sizing load based on design criteria.
Horizontal stack offsets shall be sized as required for building drains in accordance with Table 710.1(1), except as required by Section 711.3.
Vertical stack offsets shall be sized as required for straight stacks in accordance with Table 710.1(2), except where required to be sized as a building drain in accordance with Section 711.1.1.
Related Code Sections
710.1 Sanitary Drainage, Maximum Fixture Unit Load
The maximum number of drainage fixture units connected to a given size of building sewer , building drain or horizontal branch ...
Plumbing Code 2018 of Kansas > 7 Sanitary Drainage > 710 Drainage System Sizing > 710.1 Maximum Fixture Unit Load
P3005.4.2 Sanitary Drainage, Building Drain and Sewer Size and Slope
Pipe sizes and slope shall be determined from Table P3005.4.2 on the basis of drainage load in fixture units (d.f.u.) computed from Table P3004.1 ...
Residential Code 2018 of Kansas > 30 Sanitary Drainage > P3005 Drainage System > P3005.4 Drain Pipe Sizing > P3005.4.2 Building Drain and Sewer Size and Slope
917.2 Vents, Stack Size
TABLE 917.2 SINGLE STACK SIZE STACK SIZE (inches) MAXIMUM CONNECTED DRAINAGE FIXTURE UNITS Stacks less than 75 feet in height ...
403.2 Fixtures, Faucets and Fixture Fittings, Separate Facilities
for dwelling units and sleeping units. Separate facilities shall not be required in structures or tenant spaces with a total occupant load ...
Plumbing Code 2018 of Kansas > 4 Fixtures, Faucets and Fixture Fittings > 403 Minimum Plumbing Facilities > 403.2 Separate Facilities
Section 709 Sanitary Drainage, Fixture Units
Drainage fixture unit values as given in Table 709.1 designate the relative load weight of different kinds of fixtures that shall be employed ...