// CODE SNIPPET
3314.5.4 Maximum Cantilever
JUMP TO FULL CODE CHAPTER
The maximum cantilever shall be as follows.
The end of a platform 10 feet (3048 mm) or less in length shall not extend over the centerline of its support more than 12 inches (305 mm) unless the platform and its tiedown are designed by a qualified person or the platform has guardrails to prevent access to the cantilevered end.
The end of a platform more than 10 feet (3048 mm) in length shall not extend over the centerline of its support more than 18 inches (457 mm) unless the platform and its tiedown are designed by a qualified person or the platform has guardrails to prevent access to the cantilevered end.
Related Code Sections
3314.5.4 Safeguards During Construction or Demolition, Maximum Cantilever
the platform and its tiedown are designed by a qualified person or the platform has guardrails to prevent access to the cantilevered end ...
NYC Building Code 2008 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.5 Platform Construction > 3314.5.4 Maximum Cantilever
3314.5.4 Safeguards During Construction or Demolition, Maximum Cantilever
The maximum cantilever shall be as follows. The ...
NYC Building Code 2014 > 33 Safeguards During Construction or Demolition > 3314 Scaffolds > 3314.5 Platform Construction > 3314.5.4 Maximum Cantilever
2304.8.2.5 Wood, Controlled Random Pattern
(76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following: The maximum cantilevered length shall be 30 ...
NYC Building Code 2014 > 23 Wood > 2304 General Construction Requirements > 2304.8 Lumber Decking > 2304.8.2 Layup Patterns > 2304.8.2.5 Controlled Random Pattern
2304.8.2 Wood, Layup Patterns
), 3-inch (76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following: The maximum cantilevered length shall ...
NYC Building Code 2014 > 23 Wood > 2304 General Construction Requirements > 2304.8 Lumber Decking > 2304.8.2 Layup Patterns
2304.8 Wood, Lumber Decking
), 3-inch (76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following: The maximum cantilevered length shall ...