A5.209.5.1 Maximum Allowed Lighting Power
Go To Full Code Chapter
A5.209.5.1.1
For internally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 12 watts per square foot. For double-faced signs, only the area of a single face shall be used to determine the allowed lighting power.
A5.209.5.1.2
For externally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 2.3 watts per square foot. Only areas of an externally lighted sign that are illuminated without obstruction or interference, by one or more luminaires, shall be used.
Related Code Sections
A5.209.5.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Maximum Allowed Lighting Power
For internally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 12 watts per ...
A5.209.5.1 — Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Maximum Allowed Lighting Power
For internally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 12 watts per ...
A5.209.5.1 Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4], Maximum Allowed Lighting Power
For internally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 12 watts per ...
A5.209.5.1.2 Voluntary Standards for Health Facilities [OSHPD 1, 2 & 4],
For externally illuminated signs, the maximum allowed lighting power shall not exceed the product of the illuminated sign area and 2.3 watts per ...
Section 140.8 Nonresidential, High-Rise Residential and Hotel/Motel Occupancies—Performance and Prescriptive Compliance Approaches for Achieving Energy Efficiency, Requirements for Signs
, both indoor and outdoor. Each sign shall comply with either subsection (a) or (b), as applicable. (a) Maximum allowed lighting power. For internally ...