R404.1.9.2 Masonry Piers Supporting Floor Girders
JUMP TO FULL CODE CHAPTER
Masonry piers supporting wood girders sized in accordance
with Tables R602.7(1) and R602.7(2) shall be
permitted in accordance with this section. Piers supporting
girders for interior bearing walls shall have a
minimum nominal dimension of 12 inches (305 mm)
and a maximum height of 10 feet (3048 mm) from top
of footing to bottom of sill plate or girder. Piers supporting
girders for exterior bearing walls shall have a
minimum nominal dimension of 12 inches (305 mm)
and a maximum height of 4 feet (1220 mm) from top of
footing to bottom of sill plate or girder. Girders and sill
plates shall be anchored to the pier or footing in accordance
with Section R403.1.6 or Figure R404.1.5(1).
Floor girder bearing shall be in accordance with Section
R502.6.
Related Code Sections
R404.1.9.2 Foundations, Masonry Piers Supporting Floor Girders
Masonry piers supporting wood girders sized in accordance
with Tables R602.7(1) and R602.7(2) shall be
permitted in accordance with this section ...
2015 Michigan Residential Code > 4 Foundations > R404 Foundation and Retaining Walls > R404.1 Concrete and Masonry Foundation Walls > R404.1.9 Isolated Masonry Piers > R404.1.9.2 Masonry Piers Supporting Floor Girders
1809.10 Soils and Foundations, Pier and Curtain Wall Foundations
not exceed 10 times their least dimension.
Where structural clay tile or hollow concrete masonry units are used for piers supporting beams and girders ...
2015 Michigan Building Code > 18 Soils and Foundations > 1809 Shallow Foundations > 1809.10 Pier and Curtain Wall Foundations
R606.7 Wall Construction, Piers
are used for isolated
piers to support beams and girders, the cellular spaces shall be
filled solidly with grout or Type M or S mortar, except ...
2015 Michigan Residential Code > 6 Wall Construction > R606 General Masonry Construction > R606.7 Piers
2304.11.2 Wood, Floor Framing
beams are used to support a floor, they shall rest on
top of girders, or shall be supported by ledgers or blocks
securely fastened to the sides ...
2015 Michigan Building Code > 23 Wood > 2304 General Construction Requirements > 2304.11 Heavy Timber Construction > 2304.11.2 Floor Framing
2308.4.1 Wood, Girders
Girders for single-story construction or
girders supporting loads from a single floor shall be not less than 4 inches by 6 inches (102 mm by 152 mm ...
2015 Michigan Building Code > 23 Wood > 2308 Conventional Light-Frame Construction > 2308.4 Floor Framing > 2308.4.1 Girders