3306.8.2 Masonry Buildings With Wooden Floors
Go To Full Code Chapter
Demolition of masonry buildings with
wooden floors shall comply with the following requirements:
- Demolition of walls and partitions shall proceed in a systematic manner, and all work above each tier of floor beams shall be completed before any of the supporting structural members are disturbed.
- Sections of masonry walls shall not be loosened or permitted to fall in such masses as to affect the carrying capacity of floors or the stability of structural supports.
- No section of masonry wall with a height to thickness ratio greater than 22 shall be permitted to stand without the wall being braced. Such bracing shall be designed by a registered design professional.
Upcodes Diagrams
Related Code Sections
3306.8.2 Safeguards During Construction or Demolition, Masonry Buildings With Wooden Floors
Demolition of masonry buildings with wooden floors shall comply with the following requirements: Demolition of walls and partitions shall proceed ...
3306.8.2 Safeguards During Construction or Demolition, Masonry Buildings With Wooden Floors
Demolition of masonry buildings with
wooden floors shall comply with the following requirements:
Demolition of walls and partitions shall proceed ...
Article 4 Classifications [PDF] (page 4)
e. Wooden structural members supported by masonry or reinforced concrete walls shall have at least eight inches of masonry between the end ...
2109.6.2 Masonry, Bonding With Masonry Headers
Where the facing and backing (adjacent wythes) of solid masonry construction are bonded by means of masonry headers, no less than 4 percent ...
2105.2.1 Masonry, Compliance With f'm
Compressive strength of masonry shall be considered satisfactory if the compressive strength of each masonry wythe and grouted collar joint equals ...