1910.111(b)(4) Marking Refrigerated Containers
JUMP TO FULL CODE CHAPTER
Each refrigerated container shall be marked with nameplate on the outer covering in an accessible place as specified in the following:
With the notation, "Anhydrous Ammonia".
With the water capacity of the container in gallons, U.S. Standard.
With the design pressure.
With the minimum temperature in degrees Fahrenheit for which the container was designed.
The maximum allowable water level to which the container may be filled for test purposes.
With the density of the product in pounds per cubic foot for which the container was designed.
With the maximum level to which the container may be filled with liquid anhydrous ammonia.
With the name and address of the builder and the date of fabrication.
Related Code Sections
1910.111(b)(4) Hazardous Materials, Marking Refrigerated Containers
Each refrigerated container shall be marked with nameplate on the outer covering in an accessible place as specified in the following ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(4) Marking Refrigerated Containers
1910.111(b)(4)(i) Hazardous Materials,
With the notation, "Anhydrous Ammonia ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(4) Marking Refrigerated Containers > 1910.111(b)(4)(i)
1910.111(b)(4)(ii) Hazardous Materials,
With the name and address of the builder and the date of fabrication ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(4) Marking Refrigerated Containers > 1910.111(b)(4)(ii)
1910.111(b)(4)(iv) Hazardous Materials,
With the design pressure ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.111 Storage and Handling of Anhydrous Ammonia > 1910.111(b) Basic Rules > 1910.111(b)(4) Marking Refrigerated Containers > 1910.111(b)(4)(iv)
1910.110(b)(5) Hazardous Materials, Markings on Containers
Each container covered in paragraph (b)(3)(i) of this section, except as provided in paragraph (b)(3)(iv) of this section shall be marked ...
OSHA 1910 General Industry > H Hazardous Materials > 1910.110 Storage and Handling of Liquefied Petroleum Gases > 1910.110(b) Basic Rules > 1910.110(b)(5) Markings on Containers