34.6.3 Manual Protection
Go To Full Code Chapter
34.6.3.1 Portable Fire Extinguishers
34.6.3.1.1
Portable fire extinguishers shall be provided in
accordance with Section 13.6, unless 34.6.3.1.2 applies.
34.6.3.1.2
Where 11/2 in. (38 mm) hose lines are available to
reach all portions of areas with Class A fire loads, up to one-half
of the portable fire extinguishers required by Section 13.6 shall
be permitted to be omitted.
34.6.3.2 Hydrants
At locations without public hydrants, or
where hydrants are not within 250 ft (75 m), private hydrants
shall be installed in accordance with Section 13.5.