907.4.2 Manual Fire Alarm Boxes
JUMP TO FULL CODE CHAPTER
Where a manual fire alarm system is required by another section of this code, it shall be activated by fire alarm boxes installed in accordance with Sections 907.4.2.1 through 907.4.2.5.
Manual fire alarm boxes shall be located not more than 5 feet (1524 mm) from the entrance to each exit. Additional manual fire alarm boxes shall be located so that travel distance to the nearest box does not exceed 200 feet (60 960 mm).
The height of the manual fire alarm boxes shall be a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm), measured vertically, from the floor level to the activating handle or lever of the box.
Manual fire alarm boxes shall be red in color.
Where fire alarm systems are not required to be monitored by a supervising station, an approved permanent sign that reads: WHEN ALARM SOUNDS—CALL 911 shall be installed adjacent to each manual fire alarm box.
Where the manufacturer has permanently provided this information on the manual fire alarm box.
Where the manufacturer has permanently provided this information on the manual fire alarm box.
The Fire Department is authorized to require the installation of listed manual fire alarm box protective covers to prevent malicious false alarms or provide the manual fire alarm box with protection from physical damage. The protective cover shall be transparent or red in color with a transparent face to permit visibility of the manual fire alarm box. Each cover shall include proper operating instructions. A protective cover that emits a local alarm signal shall not be installed unless approved. Protective covers shall not project more than that permitted by Section 1003.3.3.
Related Code Sections
907.3 Fire Protection Systems, Manual Fire Alarm Boxes
Manual fire alarm boxes shall be installed in accordance with Sections 907.3.1 through 907.3.5 ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Manual Fire Alarm Boxes
907.4.2 Fire Protection Systems, Manual Fire Alarm Boxes
Where a manual fire alarm system is required by another section of this code, it shall be activated by fire alarm boxes installed in accordance ...
NYC Building Code 2014 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.4 Initiating Devices > 907.4.2 Manual Fire Alarm Boxes
907.3.4 Fire Protection Systems, Signs
shall be installed adjacent to each manual fire alarm box. Exception: Where the manufacturer has permanently provided this information ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Manual Fire Alarm Boxes > 907.3.4 Signs
907.3.2 Fire Protection Systems, Height
The height of the manual fire alarm boxes shall be a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm), measured vertically, from ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Manual Fire Alarm Boxes > 907.3.2 Height
907.3.3 Fire Protection Systems, Color
Manual fire alarm boxes shall be red in color ...
NYC Building Code 2008 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.3 Manual Fire Alarm Boxes > 907.3.3 Color