904.3.8.2 Manual Activation Device
Go To Full Code Chapter
A manual activation device for the fire extinguishing system, except foam-water systems, shall be installed at a location near a means of egress that is readily accessible from the cooking area and not less than 10 feet (3048 mm) nor more than 20 feet (6096 mm) from the commercial cooking appliances protected by the fire extinguishing system, or other approved location. The manual activation device shall be located a minimum of 42 inches (1067 mm) and a maximum of 48 inches (1219 mm) above the floor. The manual activation device shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to activate the fire extinguishing system. A sign or marking in accordance with FC Table 609.7 that clearly identifies the commercial cooking appliances being protected shall be posted on or adjacent to the manual activation device. The manual activation device shall be kept unobstructed at all times.
Related Code Sections
904.11.1 Fire Protection Systems, Manual System Operation
feet (6096 mm) from the kitchen exhaust system. The manual activation device shall be located at a minimum of 42 inches (1067 mm) and a maximum of 48 ...
21.6.2.1.2* Emergency Control Function Interfaces, Floor Identification
automatic initiating device.
Floors with any subsequently activated automatic initiating device(s).
Floors identified by manual means from the fire ...
907.6 Fire Protection Systems, Activation
alarm system. 2. Sprinkler water-flow devices. 3. Required manual fire alarm boxes. 4. Other required types ...
2.7.5.2.1 Electric Elevators,
position manually or automatically. (3) When the mechanical device is in the active position, it shall operate an electrical contact, which when ...