For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold shall be designed and constructed in accordance with approved engineering practices. As an alternative method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets, and the vent connectors shall have a minimum 1 foot (305 mm) rise. [NFPA 54:12.11.3.2]
Upcodes Diagrams

Related Code Sections

509.10.2.1 Water Heaters, Manifold
For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions ...
G2420.5.3 Fuel Gas, (409.5.3) Located at Manifold
Where the appliance shutoff valve is installed at a manifold, such shutoff valve shall be located within 50 feet (15 240 mm) of the appliance served ...